SECTION 262416 - PANELBOARDS: continued<br />

1.03 SUBMITTALS:<br />

A. Refer to DIVISION 01 and SECTION 260000 - BASIC ELECTRICAL REQUIREMENTS for<br />

administrative and procedural requirements for submittals.<br />

B. Includes, but not limited to, the following:<br />

1. Product Data: Submit manufacturer's data on panelboards and enclosures.<br />

a. Panelboard dimensions and weight (provide center-<strong>of</strong>-gravity information for each<br />

seismic rated panelboard).<br />

b. Complete data on circuit breakers. Submit time - current characteristic curves <strong>of</strong> all<br />

devices.<br />

c. Panelboard short-circuit interrupting capacity, and information on buses: phase,<br />

neutral, and ground.<br />

d. Information on whether panelboard is fed from top or bottom.<br />

e. Data on maximum and minimum incoming and outgoing feeder and branch circuit<br />

wire size.<br />

f. Data on door, locks, and mounting: surface or flush.<br />

g. Data on total number <strong>of</strong> poles and number <strong>of</strong> unused poles that are available for<br />

future use.<br />

PART 2 - PRODUCTS<br />

2.01 MANUFACTURERS: Subject to compliance with requirements, provide panelboard and<br />

mini-power center products <strong>of</strong> one <strong>of</strong> the following (for each type and rating <strong>of</strong> panelboard and<br />

enclosure) or approved equal:<br />

1. Crouse-Hinds Company.<br />

2. General Electric Company.<br />

3. Siemens-Energy and Automation, Inc.<br />

4. Square D Company.<br />

2.02 PANELBOARDS:<br />

A. General: Except as otherwise indicated, provide panelboards, enclosures, and ancillary<br />

components <strong>of</strong> types, size, and ratings indicated, which comply with manufacturer's standard<br />

materials and with the design and construction in accordance with published product<br />

information. Provide panelboards that shall resist the forces <strong>of</strong> a Seismic Zone 2A event<br />

without damage. Equip with proper number <strong>of</strong> panelboard switching and protective devices as<br />

required for complete installation. Provide ground fault circuit interrupter type circuit breakers<br />

where indicated. Where types, sizes, or ratings are not indicated, comply with NEC, UL, and<br />

established industry standards for those applications indicated. Provide terminals UL-rated for<br />

75ºC (minimum) conductors. All bus shall be tin plated copper. Bus shall be braced to<br />

withstand available short circuit currents indicated.<br />

B. Service Entrance Panelboards: Factory-assembled, dead-front, safety constructed, service<br />

entrance circuit breaker type panelboards in sizes and ratings indicated. Equip with panelboard<br />

switching and protective devices, <strong>of</strong> types, ratings, and characteristics indicated. Construct<br />

with anti-turn solderless lugs bolted to main bus bars, suitable for service with 480Y/277V,<br />

3-phase, 4-wire, 60 hertz system. Provide unit with incoming service connecting at top or<br />

bottom <strong>of</strong> panel as required. Provide full-sized neutral bus; provide suitable lugs on neutral<br />

bus for incoming and outgoing feeders requiring neutral connections. Provide ground bus.<br />

Provide bolt-on, molded-case, main circuit breaker and branch circuits with bolt-on,<br />

molded-case type, single-pole and multi-pole circuit breakers, with toggle handles that indicate<br />

when tripped. Where multiple-pole breakers are indicated, provide common trip for all poles.<br />