SECTION 283100 - FIRE ALARM SYSTEMS/ MASS NOTIFICATION SYSTEM: continued<br />

dedicated 3/4-inch (minimum) size conduit. IDC, SLC and NAC circuits shall be<br />

installed in separate conduit.<br />

2. Power Supplies: Provide system for operation on 120Vac power supply.<br />

3. Provide battery back-up as secondary power supply. Provide back-up battery and battery<br />

charger each with 20% spare capacity for future use. Design battery back-up to take over<br />

supply to system instantaneously. Provide battery with adequate capacity to be capable<br />

<strong>of</strong> operation <strong>of</strong> system for 60 hours under normal supervisory (non-alarm) conditions and<br />

then for 15 minutes under alarm conditions. Battery charger shall completely recharge<br />

batteries within 48 hours. Batteries shall be sealed gel-cell maintenance free type.<br />

E. Wiring System Materials: Provide basic wiring materials which comply with SECTION<br />

260533 - RACEWAYS, SECTION 260534 - ELECTRICAL BOXES AND FITTINGS, and<br />

SECTION 260516 - WIRE AND CABLES.<br />

1. Provide wire and cable in accordance with requirements <strong>of</strong> manufacturer, except as<br />

noted.<br />

2. Conductor sizes shall be AWG No. 14 or larger 600V, Type THHN or TFFN, with<br />

maximum 19 strands copper conductor, 7 strands for sizes AWG No. 16 and No. 18.<br />

3. Provide conductors with crimp on terminal ends.<br />

4. Provide conductors which are listed and approved for fire alarm usage.<br />

5. Do not provide multi-conductor fire alarm cables.<br />

6. Provide labeling on all termination points.<br />

7. Provide separate conduits for supply and return loops per NFPA 72 Class A System.<br />

8. Provide labeling at all termination, junction and pull boxes. Labeling shall be engraved,<br />

plastic labels that identify the zone and circuit contained.<br />

F. Fire Alarm Control Panels (FACP): Provide fire alarm control panel enclosures for housing<br />

devices and circuits necessary to perform required functions to service test points and to<br />

service trouble-signal points. Control panel shall comply with UL 864. Cabinet shall be<br />

lockable steel cabinet. Provide 10 keys to Contracting Officer.<br />

1. FACP shall be addressable.<br />

2. Provide control panel for operation on 120Vac supply and for 24Vac system operation<br />

with integral battery standby power source.<br />

3. Equip control panel for number <strong>of</strong> initiating zones indicated plus 10% (but not less than<br />

six spare modules).<br />

4. Provide TVSS protection <strong>of</strong> 120Vac power supply at the fire alarm control panel in a<br />

separate, adjacent enclosure.<br />

G. The Mass Notification functions shall override the FACP Notification functions. The system<br />

shall have the capability <strong>of</strong> utilizing a remote microphone station with redundant controls <strong>of</strong><br />

the notification system control panel. Class "A" Notification Appliance Circuits (NAC) shall<br />

be provided for the activation <strong>of</strong> strobe and speakers appliances. The activation <strong>of</strong> the NAC<br />

Circuits shall follow the operation <strong>of</strong> the speaker NAC circuits. Audio output shall be<br />

selectable for line level (600 ohms), 25, 70.7 or 100V output. The audio amplifier outputs<br />

shall be not greater than 100 watts RMS output. Amp shall have 50% spare capacity. The<br />

strobe NAC Circuits shall provide at least 2 amps <strong>of</strong> 24Vdc power to operate strobes and have<br />

the ability to synchronize all strobes. A hand held microphone shall be provided and, upon<br />

activation, shall take priority over any tone signal, recorded message operation in progress,<br />

while maintaining the strobe NAC Circuits activation.<br />

1. All outputs and operational modules shall be fully supervised with on-board diagnostics<br />

and trouble reporting circuits. Form "C" contacts shall be provided for system alarm and<br />

trouble conditions. Circuits shall be provided for operation <strong>of</strong> auxiliary appliance during<br />

trouble conditions. During a Mass Notification event the panel shall not generate nor<br />

283100-4 DEAN283100.DOC