SECTION 283100 - FIRE ALARM SYSTEMS/ MASS NOTIFICATION SYSTEM: continued<br />

1.04 SUBMITTALS:<br />

A. Refer to DIVISION 01 and SECTION 260000 - BASIC ELECTRICAL REQUIREMENTS,<br />

for administrative and procedural requirements for submittals.<br />

B. All submittals shall also be sent to the local Fire Marshall or "authority having jurisdiction" for<br />

approval. Each submittal shall be a complete submittal including shop drawings, annotated<br />

data sheets and calculating partial submittals will not be accepted.<br />

C. Includes, but not limited to, the following:<br />

1. Product Data: Submit manufacturer's technical product data, including specifications and<br />

installation instructions, for each type <strong>of</strong> fire alarm system component. Submit device<br />

power requirements: maximum voltage, nominal voltage, minimum voltage, amperes<br />

and watts for each device requiring power. Submit battery calculations. Submit battery<br />

charger calculations. Include standard or typical riser and wiring diagrams, and operation<br />

and maintenance instructions for inclusion in maintenance manuals.<br />

2. The use <strong>of</strong> SFPE Handbook or NFPA 72 Handbook to confirm acoustical requirements<br />

where a sounder/speaker is outside its listed spacing shall be acceptable.<br />

3. Shop Drawings: Provide shop drawings showing equipment/device locations, conduit<br />

sizes, logic diagrams, and point-to-point field wiring diagrams <strong>of</strong> entire fire alarm<br />

system. Include wiring and riser diagrams. Licensed fire protection engineer shall seal<br />

and sign the fire alarm shop drawings.<br />

4. Operation and Maintenance Manual: Submit maintenance data and parts lists for each<br />

type <strong>of</strong> fire alarm equipment installed, including furnished specialties and accessories.<br />

Include product data and shop drawings in accordance with requirements <strong>of</strong><br />

DIVISION 01. Submit when construction is 75% complete. Three copies <strong>of</strong> final<br />

manuals are required. Manuals will be required to include but not limited to:<br />

a. Full instructions on servicing and maintenance requirements.<br />

b. Operating instructions including start up, emergency shut down and start up,<br />

seasonal servicing and start up, etc.<br />

c. Contracting Officer's manuals for each item <strong>of</strong> equipment.<br />

d. All equipment wiring diagrams.<br />

e. All piping and wiring systems diagrams and operational diagrams.<br />

f. Full parts lists and exploded schematic diagrams.<br />

g. Full warranty information.<br />

h. All available manufacturer installation and O&M manuals.<br />

i. Full names, address, phone numbers, suppliers, service companies, contact numbers<br />

and other points <strong>of</strong> contact/information relative to this job.<br />

5. Certification <strong>of</strong> proper system operation, including all existing and new devices.<br />

6. The contractor shall submit all field test data per NFPA 72, including "NFPA 72<br />

Inspectors and Testing Forms." These reports shall be submitted a minimum <strong>of</strong> 30 days<br />

prior to scheduling <strong>of</strong> Final ANG acceptance Inspections/Testing and Commissioning.<br />

These documents shall be provided as a submittal for review and approval prior to<br />

scheduling acceptance inspection and testing. Final inspection will be scheduled upon<br />

approval <strong>of</strong> the submission documents.<br />

7. Commissioning checklists.<br />

8. Posted operation instructions shall be framed under glass and shall include floor plans<br />

showing all fire alarm device locations, fire alarm wiring diagrams, and fire alarm<br />

schematic diagrams. Posted instructions shall be pr<strong>of</strong>essionally prepared graphics,<br />

printed on full size sheets and shall be in color.<br />

9. As Built drawings.<br />

283100-2 DEAN283100.DOC