SECTION 262900 - MOTOR CONTROLLERS, CONTACTORS, PUSH BUTTONS, SELECTOR<br />

SWITCHES, INDICATING LIGHTS AND RELAYS: continued<br />

characteristics <strong>of</strong> the controller, motor and load furnished to provide proper protection by the<br />

main protective device, without nuisance tripping. Provide operating handle for main circuit<br />

protective mechanism with indication and control <strong>of</strong> position, with enclosure door either open<br />

or closed and capable <strong>of</strong> being locked in "OFF" position with three padlocks. Construct<br />

controller with NEMA Type 1 enclosure for indoor, dry, nonhazardous locations. Coat with<br />

manufacturer's standard color finish.<br />

F. Combination Disconnect and Wye-Delta Controllers: Provide wye-delta controllers, <strong>of</strong> sizes,<br />

ratings, electrical characteristics, and NEMA sizes indicated or required. Provide integral main<br />

thermal magnetic circuit breaker or main motor circuit protector. Manufacturer shall size and<br />

coordinate the main protective device with the characteristics <strong>of</strong> the controller, motor and load<br />

furnished to provide proper protection by the main protective device, without nuisance<br />

tripping. Construct controllers with open-circuit transition, including three pole thermal<br />

overload protection relay, fused 120V control transformer, push buttons, selector switches, and<br />

indicating lights. Equip with START-STOP push button for control. Provide controller with<br />

electrical interlocks specified and as required. Provide two normally open and two normally<br />

closed spare auxiliary contacts. Provide operating handle for disconnect main circuit<br />

protective mechanism with indication and control <strong>of</strong> position, with enclosure door either open<br />

or closed, and capable <strong>of</strong> being locked in "OFF" position with three padlocks. Construct<br />

controller with NEMA Type 1 enclosure for indoor, dry, nonhazardous locations. Coat with<br />

manufacturer's standard color finish.<br />

G. Combination Disconnect and Part Winding Controllers: Provide two-step, part-winding,<br />

alternating-current controllers, <strong>of</strong> NEMA sizes, ratings, and electrical characteristics indicated<br />

or required, suitable for use with motors with two wye-connected windings. Provide integral<br />

main thermal magnetic circuit breaker or main motor circuit protector. Manufacturer shall size<br />

and coordinate the main protective device with the characteristics <strong>of</strong> the controller, motor and<br />

load furnished to provide proper protection by the main protective device, without nuisance<br />

tripping. Controller shall have two 3-pole contactors, pneumatic timer, fused 120V control<br />

transformer, push buttons, selector switches, indicating lights, and two 3-pole manual external<br />

reset motor overload relays. Provide controller with electrical interlocks specified and as<br />

required. Provide two normally open and two normally closed spare auxiliary contacts.<br />

Provide operating handle for main circuit protective mechanism with indication and control <strong>of</strong><br />

position, with enclosure door either open or closed and capable <strong>of</strong> being locked in "OFF"<br />

position with three padlocks. Enclose controller unit in NEMA Type 1 general purpose<br />

enclosure for indoor, dry, nonhazardous locations. Coat enclosure with manufacturer's<br />

standard color finish.<br />

H. Combination Disconnect and Solid-<strong>State</strong>, Variable Frequency Drives (VFDs): Provide solidstate<br />

speed adjustment with adjustable frequency and voltage output that shall provide constant<br />

volts per hertz excitation <strong>of</strong> a three-phase, squirrel-cage induction motor up to 60 Hz. The<br />

controller shall have a 100% overload rating for one minute. The controller shall have a<br />

minimum efficiency <strong>of</strong> 95% at rated load. The controller shall operate in an ambient<br />

temperature <strong>of</strong> -10ºC to 50ºC for elevations up to 3,300 feet above sea level and within a<br />

humidity range <strong>of</strong> 0 to 95% noncondensing. The variable torque controller starting current<br />

shall be limited to 150% <strong>of</strong> the full load current.<br />

1. Enclosures shall be NEMA Type 1 for indoor, dry, nonhazardous locations. Provide wall<br />

mounted enclosures for control <strong>of</strong> motors smaller than 75 horsepower and free standing<br />

enclosures (with lifting eyes and enclosure suitable for pushing and being moved on<br />

rollers) for control <strong>of</strong> motors 75 horsepower and larger. Coat enclosure with<br />

manufacturer's standard color finish.<br />

262900-4 DEAN262900.DOC