SECTION 237314 - INDOOR DEDICATED OUTSIDE AIR UNITS: continued<br />

F. Internal Vibration Isolation: Fans shall be factory mounted with manufacturer's<br />

standard restrained vibration isolation mounting devices having a minimum static deflection <strong>of</strong><br />

2 inches.<br />

G. Motor: Comply with NEMA designation, temperature rating, service factor, enclosure type,<br />

and efficiency requirements for motors specified in SECTION 230513 - MOTORS.<br />

1. Enclosure Type: Totally enclosed, fan cooled.<br />

2. NEMA Premium (TM) efficient motors as defined in NEMA MG 1.<br />

3. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven load<br />

will not require motor to operate in service factor range above 1.0.<br />

4. Controllers, Electrical Devices, and Wiring: Comply with requirements for electrical<br />

devices and connections specified in DIVISION 26.<br />

5. Mount unit-mounted disconnect switches on exterior <strong>of</strong> unit.<br />

H. Variable Frequency Controllers: Shall be provided by DIVISION 26.<br />

2.04 COIL SECTION:<br />

A. General Requirements for Coil Section:<br />

1. Comply with ARI 410.<br />

2. Fabricate coil section to allow removal and replacement <strong>of</strong> coil for maintenance and to<br />

allow in-place access for service and maintenance <strong>of</strong> coil(s).<br />

3. Coils shall not act as structural component <strong>of</strong> unit.<br />

B. Refrigerant Coils: Coil designed for use with R-410A refrigerant, fabricated according to<br />

ARI 410, connected with soldered fittings.<br />

1. Capacity Reduction: Circuit for face control. Front to back split interlace.<br />

2. Tubes: Copper.<br />

3. Fins: Aluminum.<br />

4. Fin and Tube Joint: Mechanical bond a silver brazed.<br />

5. Coil Coating: Polymer e-coated cooling coil.<br />

6. Suction and Distributor: Seamless copper tube with brazed joints.<br />

7. Frames: Galvanized-steel channel frame, 0.052 inch.<br />

8. Ratings: Design tested and rated according to ASHRAE 33 and ARI 410.<br />

a. Working-Pressure Rating: 300 psig.<br />

9. Source Quality Control: Test to 450 psig and 300 psig underwater.<br />

2.05 WATER-SOURCE HEAT PUMP SECTION:<br />

A. Refrigerant-to-Water Heat Exchanger:<br />

1. Coaxial heat exchanger with copper water tube with enhanced heat-transfer surfaces<br />

inside a steel shell; both shell and tube leak tested to 450 psig on refrigerant side and<br />

400 psig on water side. Factory mount heat exchanger in unit on resilient rubber<br />

vibration isolators.<br />

2. Refrigerant Circuit Components:<br />

a. Sealed Refrigerant Circuit: Charge with R-410A refrigerant. Minimum <strong>of</strong><br />

2 circuits required. Intertwine circuits in refrigerant to air coil.<br />

b. Charging Connections: Service fittings on suction and liquid for charging and<br />

testing on each circuit.<br />

c. Reversing Valve: Pilot-operated sliding-type valve designed to be fail-safe in<br />

heating position with replaceable magnetic coil.<br />

d. Compressor: Hermetic scroll compressors installed on vibration isolators housed in<br />

an acoustically treated enclosure with factory-installed safeties as follows:<br />

(1) Antirecycle timer.<br />

DEAN237314.DOC 237314-5