SECTION 262900 - MOTOR CONTROLLERS, CONTACTORS, PUSH BUTTONS, SELECTOR<br />

SWITCHES, INDICATING LIGHTS AND RELAYS: continued<br />

2.04 CONTACTORS:<br />

A. Provide electrically or mechanically held lighting contactors, as indicated.<br />

B. Provide multipole: Number-poles as indicated or required.<br />

C. Each pole shall be rated 480Vac, 30 amperes ballast, and 20 amperes tungsten. Each pole shall<br />

be field convertible (NO or NC).<br />

D. Provide contactor in NEMA 1 surface mount or 3R surface mount enclosure, as indicated.<br />

E. Contactor shall have 120V, 60-Hz coil.<br />

F. Provide "Hand-Off-Automatic" selector switch in contactor cover.<br />

G. Provide red and green indicating lights in contactor cover.<br />

H. Provide an integral fused control circuit transformer <strong>of</strong> adequate volt-ampere capacity for the<br />

required control circuit loads.<br />

I. Provide NEMA 1 type enclosures with suitably sized factory standard knock-outs in bottom in<br />

indoor dry locations <strong>of</strong> enclosure. Provide NEMA 4 and 4X type with suitably sized conduit<br />

hub in top and bottom <strong>of</strong> enclosure in outdoor and wet indoor locations.<br />

J. Provide two-wire control for electrically held contactors. Provide three-wire control for<br />

mechanically held contactors.<br />

K. Provide auxiliary contacts as required, indicated and specified.<br />

L. Provide nameplate in accordance with NEC 409.110 where the minimum short-circuit rating<br />

(SCCR) shall be as indicated on the drawings.<br />

2.05 RELAYS:<br />

A. Provide industrial 600Vac relays with 10 ampere NEMA B600 rated contacts. Contact<br />

cartridges shall be removable and field convertible (NO or NC). Coil voltage rating shall be as<br />

required. Provide number <strong>of</strong> contacts as required, indicated or specified.<br />

B. Provide accessory latching and timing modules as required.<br />

C. Provide NEMA 1 enclosure when relay is mounted separately in dry indoor locations.<br />

PART 3 - EXECUTION<br />

3.01 EXAMINATION:<br />

A. Examine areas and conditions under which motor controllers and controls are to be installed.<br />

Do not proceed with the work until unsatisfactory conditions have been corrected.<br />

3.02 INSTALLATION OF MOTOR CONTROLLERS AND CONTROLS:<br />

A. Install motor controllers and controls where indicated, in accordance with equipment<br />

manufacturer's written instructions and with recognized industry practices; complying with<br />

applicable requirements <strong>of</strong> NEC, UL and NEMA standard, to ensure that products fulfill<br />

requirements.<br />

B. Tighten connectors and terminals, including screws and bolts, in accordance with equipment<br />

manufacturer's published torque tightening values for equipment connectors. Where<br />

manufacturer's torquing requirements are not indicated, tighten connectors and terminals to<br />

comply with tightening torques specified in UL Standard 468A and the National Electrical<br />

Code.<br />

C. Install fuses, <strong>of</strong> sizes indicated, and type specified in each fusible disconnect switch, if any.<br />

D. Provide seismic bracing such that the equipment will not be damaged during a Seismic Zone<br />

2A event.<br />

DEAN262900.DOC 262900-7