SECTION 283100 - FIRE ALARM SYSTEMS/ MASS NOTIFICATION SYSTEM: continued<br />

thermal sensors shall be tested with heat, and nonrenewable thermal sensors shall be<br />

tested by short-circuiting each end-<strong>of</strong>-line device's contacts. Test all Monaco radio,<br />

HVAC, door, exhaust fan, and annunciator interfaces for proper operation.<br />

6. After being signed by the Contracting Officer's Representative, submit a copy <strong>of</strong> test<br />

results in duplicate to the Contracting Officer, Contracting Officer, and Local Fire<br />

Protection Authority. Mount copy <strong>of</strong> inspection record in Lexan enclosed frame adjacent<br />

to the control panel.<br />

D. Training: Manufacturer's authorized service representative shall provide 8 hours <strong>of</strong> on-site<br />

training <strong>of</strong> the Contracting Officer's personnel on procedures related to start-up, shutdown,<br />

operation, troubleshooting, servicing, adjusting and preventative maintenance for the system.<br />

Provide Contracting Officer with 10 days advance notice <strong>of</strong> training. Provide a pr<strong>of</strong>essionally<br />

edited DVD for training on the fire alarm and HEF system.<br />

E. Spare Parts:<br />

1. General: Furnish Contracting Officer, with receipt, the following spare parts:<br />

a. Provide 10% spare initiating device <strong>of</strong> each type used (not less than 1).<br />

b. Provide one spare indicating device <strong>of</strong> each type used.<br />

c. Provide three spare fuses <strong>of</strong> each rating used.<br />

d. Provide 10% spare strobe lamps.<br />

e. Provide 2% spare detector bases (not less than 1).<br />

f. Provide 10% spare LEDs and indicating lights.<br />

g. Provide one extra end <strong>of</strong> line resister for each zone.<br />

END OF SECTION 283100<br />

DEAN283100.DOC 283100-9