SECTION 238146 - WATER-SOURCE HEAT PUMPS<br />

PART 1 - GENERAL<br />

1.01 SUMMARY:<br />

A. This Section includes the following types <strong>of</strong> water-source heat pumps:<br />

1. Concealed horizontal or vertical units, 6 tons and smaller.<br />

2. Accessories.<br />

1.02 REFERENCES:<br />

A. Applicable Standards:<br />

1. American Refrigeration Institute (ARI):<br />

a. Guideline B - Ro<strong>of</strong> Mounted Outdoor air-conditioning Installations.<br />

b. ISO-13256-1 - Water-Source Heat Pumps - Testing and Rating for Performance.<br />

2. American Society <strong>of</strong> Heating, Refrigerating and Air-conditioning Engineers (ASHRAE):<br />

a. 15 - Safety Standard for Refrigeration Systems.<br />

b. 52.1 - Gravimetric and Dust-Spot Procedures for Testing Air-Cleaning Devices Use<br />

in General Ventilation for Removing Particulate Matter (ANSI).<br />

c. 52.2 - Method <strong>of</strong> Testing General Ventilation Air-Cleaning Devices for Removal<br />

Efficiency by Particle Size (ANSI).<br />

d. 62 - Ventilation for Acceptable Indoor Air Quality.<br />

3. American Society <strong>of</strong> Heating, Refrigerating and Air-Conditioning Engineers/Illuminating<br />

Engineering Society <strong>of</strong> North America (ASHRAE/IESNA):<br />

a. 90.1 - Energy Standard for Buildings except Low-Rise Residential Buildings.<br />

4. ASTM International (ASTM):<br />

a. B88 - Seamless Copper Water Tube.<br />

b. B88M - Seamless Copper Water Tube (Metric).<br />

c. B743 - Seamless Copper Tube in Coils.<br />

d. E84 - Test Method for Surface Burning Characteristics <strong>of</strong> Building Materials.<br />

5. National Ro<strong>of</strong>ing Contractors Association (NRCA):<br />

a. Low-Slope Membrane Ro<strong>of</strong>ing Construction Details Manual, Vol. 1 (1996).<br />

6. NFPA International (NFPA):<br />

a. 70 - National Electrical Code.<br />

7. Underwriters Laboratories Inc. (UL):<br />

a. 181 - Factory-Made Air Ducts and Air Connectors.<br />

b. 1995 - Heating and Cooling Equipment.<br />

1.03 SUBMITTALS:<br />

A. General: Submit the following as specified in SECTION 230500 - BASIC MECHANICAL<br />

MATERIALS AND METHODS.<br />

B. Product Data: Include rated capacities, furnished specialties, and accessories for each model.<br />

C. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,<br />

required clearances, method <strong>of</strong> field assembly, components, and location and size <strong>of</strong> each field<br />

connection.<br />

1. Wiring Diagrams: Power, signal, and control wiring.<br />

D. Product Certificates: For each type <strong>of</strong> water-source heat pump, signed by product<br />

manufacturer.<br />

E. Field quality-control test reports.<br />

F. Operation and Maintenance Data: For water-source heat pumps to include in emergency,<br />

operation, and maintenance manuals.<br />

G. Warranty: Special warranty specified in this Section.<br />

DEAN238146.DOC 238146-1