SECTION 262900 - MOTOR CONTROLLERS, CONTACTORS, PUSH BUTTONS, SELECTOR<br />

SWITCHES, INDICATING LIGHTS AND RELAYS: continued<br />

2. Only a single 480Vac, 3-phase, 60-Hz, power input shall be required for all control and<br />

power. The controller input shall be rated 460V (+10% to -10%), three-phase, and 60-Hz<br />

(+2% to -2%). The converter shall utilize a three-phase, full-wave, diode bridge. Provide<br />

6 pulse unit. Provide fused 120V control power transformer on line side <strong>of</strong> converter.<br />

Control power transformer shall be sized for controls, space heaters, and air conditioners<br />

(if air conditioning is necessary because <strong>of</strong> ambient conditions.) The controller shall<br />

maintain a minimum lagging power factor <strong>of</strong> 0.95 at any speed or load. The controller<br />

shall have input line filtering in compliance with IEEE 519 and shall not generate<br />

harmonics <strong>of</strong> a magnitude that create power line disturbances objectionable to the local<br />

utility. Provide an input power isolation transformer UL-listed for nonlinear loads<br />

(UL 1561) with the proper "K" rating in a NEMA Type 1 enclosure, if necessary, to limit<br />

the total harmonic voltage and current distortion to valves in IEEE 519 Tables 10.1 and<br />

10.3.<br />

3. Provide integral main thermal magnetic circuit breaker or main motor circuit protector<br />

with AIC RMS SYM rating at rated voltage as indicated. Manufacturer shall size and<br />

coordinate the main protective device with the characteristics <strong>of</strong> the controller, motor and<br />

load furnished to provide proper protection by the main protective device, without<br />

nuisance tripping. The main circuit protective mechanism shall have a door interlocked,<br />

padlockable handle mechanism suitable for up to three padlocks. Provide current<br />

limiting fuse for short circuit current protection <strong>of</strong> the converter. Provide controller trip<br />

and visual indication in door for each <strong>of</strong> the following: control logic malfunction, output<br />

motor overload, output ground, output short circuit, input instantaneous overload, input<br />

inverse time overload, input overvoltage, input under-voltage, input phase-loss, input<br />

over-frequency, cabinet over-temperature and ac input surge. Unit shall trip if 150% <strong>of</strong><br />

motor full load current (or more) is drawn for 4 minutes. The controller shall be able to<br />

withstand a phase-to-phase short circuit at the output terminals without any component<br />

failure.<br />

4. The DC voltage shall be inverted with a pulse width modulated (PWM) transistor inverter<br />

to an adjustable frequency output. The output frequency stability to be +1.0% to -1.0%<br />

and the output voltage regulation to be +2% to -2%.<br />

5. Provide the following features: Provide internal factory wiring and wiring terminal strips<br />

field for the following located remote from the unit:<br />

a. Two remote stops.<br />

b. One remote start.<br />

c. One remote speed control potentiometer.<br />

d. One remote bypass on-<strong>of</strong>f input.<br />

e. Remote-Local-Off selector switch position output.<br />

f. Manual-Off-Automatic selector switch position output.<br />

g. Speed range from 30 Hz to 60 Hz.<br />

h. (0-10Vdc) (4-20 mA DC) (3-15 psig) analog input process signal follower.<br />

6. Provide the following on the door <strong>of</strong> the unit:<br />

a. Power ON indicating light.<br />

b. Motor running green indicating light.<br />

c. Motor not running red indicating light.<br />

d. Output digital frequency meter calibrated in hertz.<br />

e. Minimum speed potentiometer (30-40 Hz).<br />

f. Provide low speed boost for low speed starting <strong>of</strong> motors.<br />

g. Maximum speed potentiometer (40-60 Hz).<br />