SECTION 238240 - PROPELLER UNIT HEATERS<br />

PART 1 - GENERAL<br />

1.01 SUMMARY:<br />

A. This Section includes propeller unit heaters with electric-resistance coils.<br />

1.02 REFERENCES:<br />

A. Applicable Standards:<br />

1. American Society <strong>of</strong> Heating, Refrigerating and air-Conditioning Engineers (ASHRAE):<br />

a. 33 - Method <strong>of</strong> Testing Forced Circulation Air Cooling and Heating Coils (ANSI).<br />

2. NFPA International (NFPA):<br />

a. 70 - National Electrical Code.<br />

b. 90A - Installation <strong>of</strong> Air Conditioning and Ventilating Systems.<br />

3. Underwriters Laboratories Inc. (UL):<br />

a. 823 - Electric Heaters for Use in Hazardous (Classified) Locations.<br />

b. 2021 - Fixed and Location-Dedicated Electric Room Heaters.<br />

1.03 SUBMITTALS:<br />

A. General: Submit as specified in SECTION 230500 - COMMON WORK RESULTS FOR<br />

HVAC.<br />

B. Product Data: Include rated capacities, operating characteristics, furnished specialties, and<br />

accessories for each unit type and configuration.<br />

C. Shop Drawings: Submit the following for each unit type and configuration:<br />

1. Plans, elevations, sections, and details.<br />

2. Details <strong>of</strong> anchorages and attachments to structure and to supported equipment.<br />

3. Wiring Diagrams: Power, signal, and control wiring. Differentiate between<br />

manufacturer-installed and field-installed wiring.<br />

4. Equipment schedules to include rated capacities, operating characteristics, furnished<br />

specialties, and accessories.<br />

D. Operation and Maintenance Data: For propeller unit heaters to include in operation and<br />

maintenance manuals.<br />

1.04 QUALITY ASSURANCE:<br />

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,<br />

Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for<br />

intended use.<br />

PART 2 - PRODUCTS<br />

2.01 MANUFACTURERS:<br />

A. Manufacturers: Subject to compliance with requirements, provide products by one <strong>of</strong> the<br />

following or an approved equal:<br />

1. Brasch Manufacturing Co., Inc.<br />

2. Carrier Corp.<br />

3. Chromalox.<br />

2.02 UNIT HEATERS:<br />

A. Description: An assembly including casing, coil, fan, and motor in horizontal discharge<br />

configuration with adjustable discharge louvers.<br />

B. Comply with UL 2021.<br />

DEAN238240.DOC 238240-1