SECTION 260000 - BASIC ELECTRICAL REQUIREMENTS: continued<br />

with other systems, installations, and building components. Drawings shall be prepared on<br />

30- by 42-inch paper. Indicate locations where space is limited for installation and access and<br />

where sequencing and coordination <strong>of</strong> installations are <strong>of</strong> importance to the efficient flow <strong>of</strong><br />

the Work, including (but not necessarily limited to) the following:<br />

1. Indicate the proposed locations <strong>of</strong> major raceway systems, equipment, and materials.<br />

2. Clearances for servicing equipment, including space for equipment disassembly required<br />

for periodic maintenance.<br />

3. Exterior wall and foundation penetrations.<br />

4. Fire-rated wall and floor penetrations.<br />

5. Equipment connections and support details.<br />

6. Sizes and location <strong>of</strong> required concrete pads and bases.<br />

7. Support details.<br />

8. Indicate scheduling, sequencing, movement, and positioning <strong>of</strong> large equipment into the<br />

building during construction.<br />

9. Prepare floor plans, elevations, and appropriate details to indicate penetrations in floors,<br />

walls, and ceilings, and their relationship to other penetrations and installations.<br />

10. Prepare reflected ceiling plans to coordinate and integrate installations, air outlets, air<br />

inlets, light fixtures, communications systems' components, sprinklers, speakers, heat<br />

detectors, smoke detectors, and other ceiling-mounted devices.<br />

1.04 RECORD DOCUMENTS:<br />

A. Prepare record documents in accordance with the requirements in SECTION 017800 -<br />

CONTRACT CLOSEOUT. In addition to the requirements specified in DIVISION 01,<br />

indicate installed conditions for:<br />

1. Major raceway systems, size and location for both exterior and interior; locations <strong>of</strong><br />

control devices; distribution and branch electrical circuitry; fuse sizes and circuit breaker<br />

sizes and arrangements.<br />

2. Equipment locations (exposed and concealed), dimensioned from prominent building<br />

lines.<br />

3. Approved substitutions, Contract Modifications, and actual Equipment and Materials<br />

installed.<br />

B. Engage the services <strong>of</strong> a licensed Land Surveyor or licensed Pr<strong>of</strong>essional Engineer registered<br />

in the state in which the Project is located to record the locations and invert elevations <strong>of</strong><br />

underground installations.<br />

1.05 MAINTENANCE MANUALS:<br />

A. Prepare maintenance manuals in accordance with SECTION 017800 - CONTRACT<br />

CLOSEOUT. In addition to the requirements specified in DIVISION 01, include the following<br />

information for Equipment items:<br />

1. Description <strong>of</strong> function, normal operating characteristics and limitations, performance<br />

curves, engineering data and tests, and complete nomenclature and commercial numbers<br />

<strong>of</strong> replacement parts.<br />

2. Manufacturer's printed operating procedures to include start-up, break-in, routine and<br />

normal operating instructions; regulation, control, stopping, shutdown, and emergency<br />

instructions; and summer and winter operating instructions.<br />

3. Maintenance procedures for routine preventive maintenance and troubleshooting;<br />

disassembly, repair, and reassembly; aligning and adjusting instructions.<br />

4. Servicing instructions and lubrication charts and schedules.<br />

5. "As-Built" schematic and wiring diagrams.<br />