SECTION 260516 - WIRES AND CABLES: continued<br />

PART 2 - PRODUCTS<br />

c. Recommended maximum pulling tension and minimum bending radius <strong>of</strong> wire and<br />

cable.<br />

d. Recommended wire and cable pulling lubricants.<br />

e. All field test data.<br />

2.01 WIRE AND CABLES:<br />

A. General: Provide wire and cable suitable for the location where installed.<br />

B. Conductors: Minimum conductor size shall be #12 AWG. Except #14 AWG stranded can be<br />

used for controls unless indicated or specified otherwise. Provide solid conductors for power<br />

and lighting circuits No. 10 AWG and smaller unless indicated or specified otherwise. Provide<br />

stranded conductors for sizes No. 8 AWG and larger unless indicated or specified otherwise.<br />

C. Conductor Material: Use copper for all sizes.<br />

D. Provide wire and cable numbers that match electrical schematics.<br />

E. Provide stranded hookup wire with appropriate voltage rating and ampere rating inside <strong>of</strong> all<br />

control enclosures.<br />

2.02 CONNECTORS FOR CONDUCTORS:<br />

A. Provide UL-listed factory-fabricated, solderless metal connectors <strong>of</strong> sizes, ampacity ratings,<br />

materials, types and classes for applications and for services indicated. Use connectors with<br />

temperature ratings to or greater than those <strong>of</strong> the wires upon which used. Connectors shall be<br />

identified for the conductor material.<br />

1. Lighting and receptacle circuit connectors for No. 10 AWG and smaller shall be twist-on<br />

spring solderless connectors. Provide silicone filled twist-on watertight/raintight<br />

connectors for all lighting circuits and receptacles circuits routed outdoors or indoors in<br />

wet locations.<br />

2. Nonlighting and nonreceptacle circuit connectors for No. 12, No. 10 AWG, and<br />

connectors for No. 8 AWG and larger shall be solderless connectors.<br />

3. All uninsulated joints shall be taped to provide an insulation value equal to that <strong>of</strong> the<br />

wire.<br />

PART 3 - EXECUTION<br />

3.01 WIRING METHOD:<br />

A. Use the following wiring methods as indicated:<br />

1. Wire and Cable: Install all wire in raceway (except if indicated or specified otherwise).<br />

2. 600V Feeder and Branch Circuit Cable:<br />

a. 480V, 277V, 240V, 208V, 120V and Control Cables for 120V Circuits (and Lower<br />

Voltage): Type THHN/THWN rated 600Vac.<br />

3. 600V Service Entrance Cable Type USE: For underground service to buildings where<br />

indicated. Rated 600Vac.<br />

4. Medium voltage cable where indicated. Medium cable shall be 15 kV, 133% EPR. The<br />

15 kV cable shall be concentric-lay-strand, Class B conductor. Provided s<strong>of</strong>t drawn<br />

copper cable complying with ASTM B3.<br />

a. All medium voltage splices and cable terminations shall be made by a certified<br />

medium voltage cable splicer.<br />

260516-2 DEAN260516.DOC