SECTION 260536 - CABLE TRAY: continued<br />

2. Materials and Finishes: Material and finish specifications for each wire basket type are<br />

as follows:<br />

a. Electroplated Zinc: Straight sections shall be made from steel meeting the<br />

minimum mechanical properties <strong>of</strong> ASTM A510 and shall be electroplated zinc in<br />

accordance with ASTM B633 SC2.<br />

b. Stainless Steel: Straight sections and accessories shall be made from AISI<br />

Type 304 Stainless Steel.<br />

C. Tubular Style Cable Runway:<br />

1. Runway shall be ladder type with 1-1/2-inch stringer height with welded rungs.<br />

2. Runway shall be 12 inches wide and 10 feet long with rungs spaced 9 inches on center, or<br />

as shown on drawings.<br />

3. Cable runway shall be Flat Black powder coat.<br />

D. Fittings and Accessories:<br />

1. Provide horizontal elbows, vertical elbows, horizontal tees, vertical tees, horizontal cross,<br />

reducers, solid flanged covers, ventilated covers, peaked covers, cover clamps, metal<br />

barrier strips, end plates, connector plates, hinged splice plates, reducing splice plates,<br />

expansion joint plates, bonding jumpers, box connectors, cable dropouts, cable clamps,<br />

and supports required.<br />

2. Fittings and connector plates shall provide the same load capacity as the straight sections.<br />

3. All fittings and accessories shall be from the cable tray manufacturer.<br />

4. Provide warning signs with 1-1/2-inch high black letters on a yellow background that<br />

reads: "WARNING! Not to be used as a walkway, ladder, or support for ladders or<br />

personnel." Provide on the outside <strong>of</strong> each side <strong>of</strong> the cable tray at 10-feet intervals.<br />

E. Supports:<br />

1. Trapeze and center hung type supports shall utilize galvanized, manufactured framing<br />

channels, threaded rods, beam clamps, cable tray hold down clamps, etc. Supports shall<br />

support cable tray without noticeable deflection <strong>of</strong> support members.<br />

2. Provide galvanized rods, anchors, inserts, clamps, spacers, shims, bolts, nuts, and<br />

miscellaneous steel as required.<br />

3. Supports shall be adequate to support cable tray with cables indicated plus cables<br />

indicated for future installation (if any).<br />

4. Supports shall be designed for Seismic Category D.<br />

PART 3 - EXECUTION<br />

3.01 GENERAL:<br />

A. Install cable tray, fittings, and accessories level, plumb and as required, in accordance with<br />

manufacturer's written instructions, applicable requirements <strong>of</strong> NEMA and NEC, and with<br />

recognized industry standard practices to fulfill project requirements.<br />

B. Sufficient space shall encompass cable trays to permit access for cable installation.<br />

C. Where cable trays contain circuits <strong>of</strong> different noise levels, the horizontal and vertical spacing<br />

between outside surfaces <strong>of</strong> the cable trays shall not be less than indicated below (unless<br />

specified otherwise, indicated otherwise, or required otherwise by the equipment<br />

manufacturer):<br />

1. Noise Level 1 Circuits: Analog circuits less than 50V, digital signals less than 12V, or<br />

telephone circuits.<br />

2. Noise Level 2 Circuits: Analog circuits greater than 50V or digital circuits greater than<br />

12V.<br />

3. Noise Level 3 Circuits: 120Vac or DC circuits operating at less than 20 amperes.<br />

260536-2 DEAN260536.DOC