14.07.2014 Views

Specifications - State of Delaware

Specifications - State of Delaware

Specifications - State of Delaware

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SECTION 260533 - RACEWAYS: continued<br />

15. Provide explosion-pro<strong>of</strong> flexible metal conduit where indicated or required.<br />

16. Provide explosion-pro<strong>of</strong> conduit seals where indicated or required. Fill conduit seals<br />

with sealant as recommended by the manufacturer.<br />

17. Conduit installed above suspended ceilings shall comply with the following:<br />

a. Install exposed conduits and extensions from concealed conduit systems neatly and<br />

parallel with or at right angles to walls <strong>of</strong> building or structure.<br />

b. Install exposed conduit work so as not to interfere with ceiling inserts, windows,<br />

doors, lights, ventilation ducts or outlets.<br />

c. Support exposed conduits by use <strong>of</strong> hangers, clamps, or clips. Support conduits on<br />

each side <strong>of</strong> bends and on spacing not to exceed NEC requirements.<br />

18. For Branch circuits, route conduit above grade. Conduits may be routed in slab with<br />

approval <strong>of</strong> ANG.<br />

C. Concealed Conduits:<br />

1. Metallic raceways in floors below grade or outside are to have conduit threads painted<br />

with corrosion inhibiting compound before couplings are assembled. Draw up coupling<br />

and conduit sufficiently tight to ensure watertightness.<br />

2. Install underground conduits a minimum <strong>of</strong> 36 inches below finished grade.<br />

D. Conduits in Concrete Slabs:<br />

1. Place conduits between bottom reinforcing steel and top reinforcing steel.<br />

2. Place conduits either parallel or at 90 degrees to main reinforcing steel.<br />

3. Separate conduits by not less than the outside diameter <strong>of</strong> the largest conduit to ensure<br />

proper concrete bond.<br />

4. Conduits crossing in slab must be reviewed for proper cover by the Contracting Officer's<br />

Representative.<br />

5. Embedded conduit outside diameter shall not exceed 1/3 <strong>of</strong> slab thickness. Provide a<br />

minimum <strong>of</strong> 3/4 inch <strong>of</strong> concrete cover.<br />

6. Embedded conduit shall be PVC-coated rigid steel conduit.<br />

E. Install conduits so as not to damage or run through solid structural members. Avoid horizontal<br />

or cross runs in building partitions or interior walls. Conduits shall run vertically in all walls to<br />

above ceilings.<br />

F. Exposed Conduits:<br />

1. Install exposed conduits and extensions from concealed conduit systems neatly and<br />

parallel with or at right angles to walls <strong>of</strong> building or structure.<br />

2. Install exposed conduit work so as not to interfere with ceiling inserts, windows, doors,<br />

lights, ventilation ducts or outlets.<br />

3. Support exposed conduits by use <strong>of</strong> hangers, clamps, or clips. Support conduits on each<br />

side <strong>of</strong> bends and on spacing not to exceed NEC requirements.<br />

4. Run conduit for outlets on waterpro<strong>of</strong> walls exposed. Set anchors for supporting conduit<br />

on waterpro<strong>of</strong> wall in waterpro<strong>of</strong> cement.<br />

5. Above requirements for exposed conduits also apply to conduits installed in space above<br />

suspended ceilings and in crawl spaces.<br />

G. Nonmetallic Conduits:<br />

1. Provide only where indicated. Do not install in hazardous locations (unless noted<br />

otherwise).<br />

2. Make solvent cemented joints in accordance with recommendations <strong>of</strong> manufacturer.<br />

3. Install PVC conduits in accordance with NEC and in compliance with local utility<br />

practices.<br />

DEAN260533.DOC 260533-7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!