SECTION 262416 - PANELBOARDS<br />

PART 1 - GENERAL<br />

1.01 SUMMARY:<br />

A. This Section specifies panelboards, including cabinets and boxes, as indicated by drawings and<br />

schedules, and as specified herein.<br />

B. Types <strong>of</strong> panelboards and enclosures required for the project include the following:<br />

1. Service entrance panelboards.<br />

2. Power distribution panelboards.<br />

3. Lighting and small power panelboards.<br />

4. Emergency power panelboards.<br />

C. Related Work Specified Elsewhere:<br />

1. Wires/cables, electrical boxes, fittings, and raceways required in conjunction with the<br />

installation <strong>of</strong> panelboards and enclosures: Other DIVISION 26 Sections.<br />

2. SECTION 260553 - ELECTRICAL IDENTIFICATION.<br />

3. SECTION 260526 - GROUNDING.<br />

1.02 REFERENCES:<br />

A. Applicable Standards (comply with applicable requirements <strong>of</strong> the following standards):<br />

1. National Electrical Manufacturers Association (NEMA):<br />

a. 250 - Enclosures for Electrical Equipment (1,000V Maximum).<br />

b. PB1 - Panelboards.<br />

c. PB1.1 - Instructions for Safe Installation, Operation, and Maintenance <strong>of</strong><br />

Panelboards Rated 600V or Less.<br />

d. PB2.2 - Application Guide for Ground-Fault Protective Devices for Equipment.<br />

2. National Fire Protection Association (NFPA):<br />

a. 70 - National Electrical Code (NEC): Comply with applicable local code<br />

requirements <strong>of</strong> the authority having jurisdiction and NEC as applicable to<br />

installation and construction <strong>of</strong> electrical panelboards and enclosures.<br />

3. Underwriters Laboratories (UL): Provide panelboard units which are UL-listed and<br />

labeled.<br />

a. 50 - Electrical Cabinets and Boxes.<br />

b. 67 - Electrical Panelboards.<br />

c. 486A - Wire Connectors and Soldering Lugs for Use with Copper Conductors.<br />

d. 489 - Molded Case Circuit Breakers and Circuit Breaker Enclosures.<br />

e. 869 - Electrical Service Equipment.<br />

f. 1053 - Ground-Fault sensing and Relaying Equipment.<br />

g. 1283 - Electromagnetic Interference Filters.<br />

h. 1449 - Transient Voltage Surge Suppressors.<br />

i. Special Use Markings: Provide panelboards constructed for special use with<br />

appropriate UL markings which indicate that they are "Suitable for Use As Service<br />

Equipment."<br />

4. Federal Specification (FS) Compliance: Comply with applicable requirements <strong>of</strong> the<br />

following standards:<br />

a. FS W-C-375 Series - Molded-Case Circuit-Breakers, Branch Service and Circuit.<br />

b. FS W-S-115 - Power Distribution Panel.<br />

c. FS W-S-865 - Surface-Mounted Switch Box (Enclosed).<br />

d. FS W-F-870/Gen - Fuseholders and Fuseclips.<br />

DEAN262416.DOC 262416-1