SECTION 262816 - CIRCUIT AND MOTOR DISCONNECT SWITCH<br />

PART 1 - GENERAL<br />

1.01 SUMMARY:<br />

A. This Section specifies circuit and motor disconnects.<br />

B. Related Work Specified Elsewhere: The following Sections contain requirements that relate to<br />

this Section.<br />

1. Fuses: SECTION 262813.<br />

2. Manual switches used as motor disconnects: SECTION 262726 - WIRING DEVICES.<br />

3. Combination type starters which incorporate disconnect switches in the same enclosure<br />

as the starter and manual motor starters which include the disconnect function as part <strong>of</strong><br />

the starter switch assembly: SECTION 262900 - MOTOR CONTROLLERS,<br />

CONTACTORS, PUSH BUTTONS, SELECTOR SWITCHES, INCLUDING LIGHTS<br />

AND RELAYS.<br />

4. Electrical Identification: SECTION 260553.<br />

1.02 REFERENCES:<br />

A. Applicable Standards: Comply with applicable requirements <strong>of</strong> the following standards.<br />

1. National Electrical Manufacturers Association (NEMA):<br />

a. 250 - Enclosures for Electrical Equipment (1,000V maximum).<br />

b. KS 1 - Enclosed Switches.<br />

2. National Fire Protection Association (NFPA):<br />

a. 70 - National Electrical Code (NEC).<br />

3. Underwriters Laboratories (UL):<br />

a. 98 - Enclosed and Dead-Front Switches.<br />

b. 869 - Electrical Service Equipment.<br />

c. 894 - Switches for Use in Hazardous (Classified) Locations.<br />

d. 977 - Fused Power-Circuit Devices.<br />

1.03 SUBMITTALS:<br />

A. Refer to DIVISION 01 and SECTION 260000 - BASIC ELECTRICAL REQUIREMENTS for<br />

administrative and procedural requirements for submittals.<br />

B. Includes, but not limited to, the following:<br />

1. Product data for each type <strong>of</strong> product specified.<br />

2. Ampere rating and fused switch short-circuit interrupting ratings.<br />

3. Maintenance data for circuit and motor disconnects for inclusion in Operation and<br />

Maintenance Manual specified in DIVISION 01 and SECTION 260000 - BASIC<br />

ELECTRICAL REQUIREMENTS.<br />

PART 2 - PRODUCTS<br />

2.01 CIRCUIT AND MOTOR DISCONNECT SWITCHES:<br />

A. General: Provide 3-pole circuit and motor disconnect switches in types, sizes, duties, features,<br />

ampere ratings, short-circuit interrupting ratings, energy withstand ratings, and enclosures as<br />

indicated. Provide NEMA 1 enclosure for indoor dry locations. For outdoor disconnect<br />

switches and other indicated wet locations (including hangar bay), provide NEMA 3R<br />

enclosures with raintight hubs. Provide enclosure suitable for hazardous location where<br />

indicated. Switch mechanism shall be interlocked with door mechanism to prevent door from<br />

opening when switch is closed and to prevent switch from being closed when door is open<br />

(provide defeat <strong>of</strong> this interlock to be used by qualified personnel.) Switch mechanism shall<br />