SECTION 283100 - FIRE ALARM SYSTEMS/ MASS NOTIFICATION SYSTEM: continued<br />

J. Fire Alarm Devices: Provide manufacturer's standard construction <strong>of</strong> the following types and<br />

characteristics.<br />

1. Nonaddressable Automatic Heat Detectors shall comply with UL 521:<br />

a. Rate-compensated, 24Vdc, 160ºF, spot type, restorable, Fenwal #27121-0-160, or<br />

approved equal. Provide one terminal strip in each heat detector back box to join<br />

the heat detector pig-tails and the field wiring. Do not terminate the two conductors<br />

(from the other cross zone) that compass directly through the back box to next<br />

conductor. For use in hangar.<br />

2. Nonaddressable Automatic Smoke (Combustion Products) Detectors: Provide<br />

manufacturer's standard construction automatic smoke detectors <strong>of</strong> the following types.<br />

a. Photoelectronic smoke detector, 24Vdc, spot types, with pulsed infrared LED light<br />

source for operation on voltage indicated. Design detector for mounting on<br />

interchangeable type base. Nominal sensitivity shall be 2.5%-3.5% per foot<br />

obscuration when tested per UL 268. Provide self-restoring smoke detector which<br />

does not require resetting. Provide flashing LED indicator for normal operation<br />

which changes to steady on alarm condition. Detector shall comply with UL 268.<br />

Provide where indicated.<br />

b. In-duct photoelectronic type, 24Vdc, with integral and remote test-reset-<strong>of</strong>f keyed<br />

switch and remote LED alarm light. Provide sampling tubes <strong>of</strong> design and<br />

dimension as recommended by the manufacturer for the specific duct size where it<br />

is applied. Detector shall comply with UL 268A. Provide adjacent "Test-Off-<br />

Reset" keyed switch mounted 84 inches above the finished floor.<br />

3. Flow Switch: Nonaddressable vane type water flow switches tested at 300 pounds per<br />

square inch that shall activate on a flow <strong>of</strong> 10 gallons per minute (minimum) rated<br />

24Vdc.<br />

4. Pressure Switch: Nonaddressable pressure type water flow switch, rated 24Vdc.<br />

5. Tamper Switch: Nonaddressable valve supervisory switches shall be mounted to signal<br />

trouble between the first and second revolution <strong>of</strong> the valve wheel, removal <strong>of</strong> the switch,<br />

or opening the cover <strong>of</strong> the switch.<br />

6. Audible and Visual Alarms:<br />

a. Horns: Provide manufacturer's standard construction, 24Vdc, fire alarm horn with<br />

the following features. Horn shall not exceed 110 dBA at 10 feet.<br />

(1) One-Tone: Three-pulse temporal pattern coded signal with general alarm<br />

(steady horn tone that matches existing base standard).<br />

(2) Surface mounted (with grille) in unfinished areas and outdoors.<br />

(3) Semi-flush mounted at dry indoor locations.<br />

(4) Single projection, unless indicated otherwise.<br />

b. Speakers shall conform to the applicable requirements <strong>of</strong> UL 1480. Speakers shall<br />

have six different sound output levels and operate with audio line input levels <strong>of</strong><br />

100Vac, 70Vac, 7Vac, and 25Vac, by means <strong>of</strong> selectable tap settings. Tap settings<br />

shall include taps <strong>of</strong> 1/4, 1/2, 1, 2, and 8 watts. Speakers shall incorporate a high<br />

efficiency speaker for maximum output at minimum power across a frequency<br />

range <strong>of</strong> 400 to 4,000 Hz, and shall have a sealed back construction. Speakers shall<br />

be capable <strong>of</strong> installation on standard 4 inch square electrical boxes. All polarity<br />

supervision <strong>of</strong> circuit wiring via the Fire Alarm Control Panel and the Mass<br />

Notification Control Panel.<br />

7. Visual Alarm Synchronized Strobes.<br />

a. Clear or white lens, lettered red "FIRE" in 1-inch high letters, for Fire Alarm and<br />

AMBER lens, lettered red "ALERT" for Mass Notification.<br />

283100-6 DEAN283100.DOC