SECTION 260529 - SUPPORTING DEVICES AND SEALS: continued<br />

G. Install fire and smoke stop compounds at all penetrations <strong>of</strong> fire rated walls, floors, ceilings<br />

and ro<strong>of</strong>s. Install fire and smoke stop compounds in accordance with manufacturer's<br />

instructions to provide a fire seal rating equal to or greater than that <strong>of</strong> the surface penetrated.<br />

H. Provide seismic support and bracing for all multiple conduit support trapezes plus individually<br />

supported conduit 2-1/2 inches and larger such that the supports shall resist the forces <strong>of</strong> a<br />

Seismic Zone 2A event without collapse.<br />

I. Provide seismic support and bracing for all cable tray such that the support shall resist the<br />

forces <strong>of</strong> a Seismic Zone 2A event without collapse.<br />

J. Provide mounting on all overhead utilities and other fixtures weighing 31 pounds or more to<br />

minimize the likelihood that they will fall. Design all equipment to resist forces <strong>of</strong> 0.5 times<br />

the equipment weight on any direction and 1.5 times the equipment weight in the downward<br />

direction.<br />

END OF SECTION 260529<br />

260529-4 DEAN260529.DOC