SECTION 264300 - TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS): continued<br />

4. Internal connections associated with the suppression filter system and subject to surge<br />

currents shall be made with solderless compression type lugs and shall be bolted to the<br />

bus bars in order to reduce overall system impedance.<br />

5. No plug-in component modules, quick-disconnect terminal, nonfield replaceable fusing,<br />

or printed circuit boards shall be used in surge current carrying paths.<br />

C. Unit Status Indicators:<br />

1. The unit shall include externally visible LED visual status indicators that monitor the online<br />

status <strong>of</strong> each phase <strong>of</strong> the unit.<br />

2.03 TVSS PERFORMANCE AND TESTING:<br />

A. TVSS maximum continuous operating voltage (MCOV) shall be capable <strong>of</strong> sustaining 115% <strong>of</strong><br />

the facility's nominal operating voltage continuously without degradation.<br />

B. Protection Modes: In accordance with NEMA standard LS 1, the unit shall provide protection<br />

in all modes. Wye configured systems shall provide Line-to-Neutral, Line-to-Ground, Line-to-<br />

Line, and Neutral-to-Ground protection. Delta configured systems shall provide Line-to-Line<br />

protection in ungrounded systems, and Line-to-Line and Line-to-Ground protection in<br />

grounded systems.<br />

C. Single Pulse Surge Current Capacity: Based on ANSI/IEEE C62.41 and in accordance with<br />

NEMA Publication No. LS-1-1992 [R2000], the tested single pulse surge current capacity, in<br />

amps, for each mode <strong>of</strong> protection <strong>of</strong> the unit shall be no less than as follows:<br />

Exposure Level L-L L-N L-G N-G<br />

Panelboard Prefix<br />

Designations<br />

Distribution Panelboards 80,000 80,000 80,000 80,000 SE, SEP, SW, WLP, 2LP<br />

Branch Panelboards 50,000 50,000 50,000 50,000 ESP, SH0, WSP, 2SP<br />

D. Unit Suppression Voltage Ratings: The TVSS published suppression voltage ratings shall be<br />

the UL 1449 listed suppression voltage ratings tested and assigned by Underwriters<br />

Laboratories.<br />

UL 1449 Ratings<br />

UL 1449 Suppression Voltage Rating<br />

Electrical System Voltage Phases without fused disconnect with fused disconnect<br />

120/208 3 400V 500V<br />

277/480 3 800V 1,000V<br />

480 3 1,500V 1,500V<br />

An additional rating <strong>of</strong> 330V can be achieved for 120/208V systems when two or more units<br />

are used with a separation <strong>of</strong> at least 100 feet.<br />

E. High Frequency Extended Range Power Filter:<br />

1. The unit shall include a high frequency extended range power filter and shall be UL 1283<br />

listed as an Electromagnetic Interference Filter.<br />

2. The filter shall reduce fast rise-time, high frequency, error-producing transients, and<br />

electrical line noise to harmless levels, thus eliminating disturbances which may lead to<br />

electronic system upset.<br />

3. The system shall be tested to MIL-STD 220A for electrical line noise attenuation per<br />

50 Ohm insertion loss measurement method <strong>of</strong> RF frequencies up to 100 MHz.<br />

DEAN264300.DOC 264300-3