628 Alarm management<br />

Defining the notifications<br />

A list of available notification types is shown in the Main Script Wizard window. There<br />

are six available notification types:<br />

E-Mails (SMS)<br />

Numeric Pagers<br />

Alphanumeric Pagers<br />

Up-Stream SNMP <strong>Manager</strong>s<br />

When defining notifications to "Up-stream SNMP <strong>Manager</strong>s", the major trap<br />

number and minor trap number are requested. The major trap number corresponds<br />

to the Enterprise branch of the SNMP OID tree, and is always "6". The minor trap<br />

number corresponds to alarm severity values defined in the OTM Open Alarm MIB,<br />

and not those of the source devices. The following values should be used for the<br />

minor trap number:<br />

1 - critical<br />

2 - major<br />

3 - minor<br />

4 - warning<br />

5 - info<br />

6 - clear<br />

Modems<br />

Files<br />

Click on one of the notification types to open the corresponding definitions window.<br />

You use the definition window to edit notification parameters. Figure 293 shows the<br />

E-Mail Notification Definition window.<br />