SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

d. Cast Iron Threaded Flanges: ANSI B16.1, Class 250; raised ground face, bolt spot<br />

faced.<br />

e. Cast Bronze Flanges: ANSI B16.24, Class 300; raised ground face, bolt holes spot<br />

faced.<br />

C. Grooved Mechanical Joints and Fittings. Joints and fittings shall be designed for not less than<br />

175 psi service and shall be the product of the same manufacturer as submitted in shop<br />

drawing equipment review; segmented welded fittings shall not be used. Fitting and<br />

coupling houses shall be malleable iron conforming to ASTM A 47/A 47M, Grade 32510;<br />

ductile iron conforming to ASTM A 536, Grade 65-45-12.<br />

1. Grooved Mechanical Couplings. Couplings shall be of ductile or malleable iron housing,<br />

a synthetic rubber gasket of a central cavity pressure-responsive design; with nuts,<br />

bolts, locking pin, locking toggle, or lugs to secure roll-grooved pipe and fittings.<br />

2. Gaskets. Gaskets shall be of silicon compound and approved for dry fire protection<br />

systems. Gasket shall be the flush type that fills the entire cavity between the fitting<br />

and the pipe. Nuts and bolts shall be heat-treated steel conforming to ASTM A 183<br />

and shall be cadmium plated or zinc electroplated.<br />

D. Flanges. Flanges shall conform to NFPA 13 and ASME B16.1. Gaskets shall be non-asbestos<br />

compressed material in accordance with ASME B16.21, 1/16 inch thick, and full face or<br />

self-centering flat ring type.<br />

1. Bolts. Bolts shall be ASTM A 449, Type 1 and shall extend no less than three full threads<br />

beyond the nut with bolts tightened to the required torque.<br />

2. Nuts. Nuts shall be hexagon type conforming to ASME B18.2.2.<br />

3. Washers. Washers shall meet the requirements of ASTM F 436. Flat circular washers<br />

shall be provided under all bolt heads and nuts.<br />

E. Pipe Hangers. Hangers shall be listed or approved for use with a fire protection system, in<br />

accordance with NFPA 13, and shall be of a type suitable for the application, construction,<br />

and pipe type and size to be supported.<br />

F. Seismic Sway Bracing. Seismic Sway Braces shall be comprised of components listed or<br />

approved for use with a fire protection system, in accordance with NFPA 13, and shall be of<br />

a type suitable for the application, construction, and pipe type and size to be braced.<br />

Component selection shall be validated with seismic sway bracing calculations.<br />

G. Valves and Strainers. Valves shall be supervised in accordance with NFPA 13 and governing<br />

DOE and Hanford Site requirements.<br />

1. Outside Screw and Yoke (OS&Y) Gate Valves. Manually operated gate valves shall be<br />

OS&Y type and shall be listed or approved for use with a fire protection system.<br />

2. Butterfly Valves. Manually operated butterfly valves shall be of indicating type and shall<br />

be listed or approved for use with a fire protection system<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 211313 - 8