Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

D. Piping Material Certification: Signed by Seller certifying that piping materials comply with<br />

ASME B31.3 requirements.<br />

E. Certificates of Shop Inspection and Data Report for piping: As required by ASME B31.3 and<br />

that the piping has been designed, manufactured and constructed in accordance with the Seller’s<br />

QA plan.<br />

F. Weld Inspection Reports<br />

The Seller shall prepare and submit weld Inspection reports that include the following information:<br />

1. Weld Map identifying weld numbers showing relative positions of pressure containing<br />

welds and attachment welds to pressure retaining components; do not reuse weld numbers.<br />

If a weld is completely replaced, assign a new number,<br />

2. Weld procedures utilized,<br />

3. Procedure qualification records (PQR) number,<br />

4. Acceptance criteria,<br />

5. Fit-up inspection (if required),<br />

6. Welder identification number,<br />

7. Filler metal heat/lot number,<br />

8. Base material heat number,<br />

9. Nondestructive examination (NDE) methods and results,<br />

10. Inspector Identification (signature or stamp and date),<br />

11. All weld repairs shall be documented in an NCR. The NCR disposition shall be approved<br />

by the Buyer.<br />

G. Field quality-control test reports.<br />

H. Operation and Maintenance Data: For Compressed Air piping specialties to include in<br />

emergency, operation, and maintenance manuals.<br />

I. The final data package shall include at a minimum:<br />

1. Completed shop travelers,<br />

2. Certified Material test reports for base materials and filler materials (CMTR’s),<br />

3. Inspection and test reports.<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221513 - 3