<strong>SECTION</strong> 074219 – FIRE RESISTIVE-CORE METAL WALL PANELS<br />

PART 1 - GENERAL<br />

1.1 SUMMARY<br />

A. Section Includes:<br />

1. Fire resistive mineral wool-core metal wall panels.<br />

1.2 PERFORMANCE REQUIREMENTS<br />

A. Structural Performance: Metal wall panel assemblies shall withstand the effects the following<br />

loads and stresses within limits and under conditions indicated, based on testing according to<br />

ASTM E 330:<br />

1. Wind Loads: Determine loads based on the following minimum design wind pressures:<br />

a. Uniform pressure of 30 lbf/sq. ft., acting inward or outward.<br />

2. Deflection Limits: Metal wall panel assemblies shall withstand wind loads with<br />

horizontal deflections no greater than 1/240 of the span.<br />

B. Air Infiltration: Air infiltration shall not exceed .04 cfm per square foot of wall area when<br />

tested per ASTM E 283 at a static pressure of 12.0 psf.<br />

C. Static Water Penetration: There shall be no uncontrolled water penetration through the panel<br />

joints at a static pressure of 20.0 psf when tested per ASTM E 331.<br />

D. Surface Burning Characteristics: The insulated core shall have been tested in accordance with<br />

ASTM E 84 for surface burning characteristics. The core shall have a maximum flame spread<br />

of zero and a maximum smoke developed rating of zero.<br />

E. Fire Resistance: Metal wall panel assemblies shall meet the requirements of fire endurance<br />

rating for nonbearing wall in accordance with UL 263 Fire Endurance Tests, Design No. U050<br />

and ASTM E 119 Fire Test of Building Construction and Materials.<br />

1. The finished panel in a seven inch thickness shall meet the requirements of a two hour<br />

fire endurance rating.<br />

2. Through-Penetrations: The two hour fire rated wall panel shall meet the requirements of<br />

composite panel penetration conditions listed by UL and in accordance with ASTM E<br />

814 Fire Tests of Through-Penetration Fire Stops. Maximum diameter of opening is 6<br />

and 7/8”. Openings can be located on or off panel unit joints.<br />

1.3 ACTION SUBMITTALS<br />

A. Product Data: For each type of product indicated.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 074219 - 1