Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

5) Motor speed (rpm).<br />

6) Set-point frequency (Hertz).<br />

d. Remote indication interface with a minimum of 2 dry circuit relay outputs (120-V<br />

ac, 1 A) for remote indication of the following:<br />

1) Motor running.<br />

2) Set-point speed reached.<br />

3) Fault and warning indication (overtemperature or overcurrent).<br />

4) High- or low-speed limits reached.<br />

15. Communications: RS485 interface allows VFC to be used with an external system within<br />

a multidrop LAN configuration. Interface shall allow all parameter settings of VFC to be<br />

programmed via BMS control. Provide capability for VFC to retain these settings within<br />

the nonvolatile memory.<br />

16. Integral Disconnecting Means: NEMA KS 1, nonfusible switch with lockable handle.<br />

17. Accessories:<br />

2.4 COIL <strong>SECTION</strong><br />

a. Devices shall be factory installed in controller enclosure unless otherwise<br />

indicated.<br />

b. Push-Button Stations, Pilot Lights, and Selector Switches: NEMA ICS 2, heavyduty<br />

type.<br />

c. Standard Displays:<br />

1) Output frequency (Hertz).<br />

2) Set-point frequency (Hertz).<br />

3) Motor current (amperes).<br />

4) DC-link voltage (volts direct current).<br />

5) Motor torque (percent).<br />

6) Motor speed (rpm).<br />

7) Motor output voltage (volts).<br />

A. General Requirements for Coil Section:<br />

1. Comply with ARI 410.<br />

2. Fabricate coil section to allow removal and replacement of coil for maintenance and to<br />

allow in-place access for service and maintenance of coil(s).<br />

3. Coils shall not act as structural component of unit.<br />

4. Seismic Fabrication Requirements: Fabricate coil section, internal mounting frame and<br />

attachment to coils, and other coil section components with reinforcement strong enough<br />

to withstand seismic forces defined in Division 23 Section "Vibration and Seismic<br />

Controls for HVAC Piping and Equipment" when coil-mounting frame and air-handlingunit<br />

mounting frame are anchored to building structure.<br />

2.5 AIR FILTRATION <strong>SECTION</strong><br />

A. General Requirements for Air Filtration Section:<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 237313 - 8