Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

cooling/lubrication filter, and thermal bypass valve. The lubricant filter shall have a 25<br />

micron rating (maximum) and shall be a screw-on type with a differential pressure<br />

indicator.<br />

9. The compressor unit shall incorporate an air cooled lubricant cooler of sufficient size to<br />

insure that the lubricant temperature from the compressor shall not exceed 190 deg F with<br />

105 deg F ambient at full load. A thermostatic valve shall be included to insure that the<br />

discharge lubricant temperature does not fall below 170 degrees F. on cold days.<br />

10. The compressor shall incorporate a synthetic lubricant to prolong the bearing life and<br />

extend the lubricant life to at least 8,000 hours under normal operating conditions.<br />

11. Air/Lubrication Receiver and Separation System: The unit shall be equipped with a<br />

combination air receiver/lubricant reservoir assembly, rated at 235 PSIG. This assembly<br />

is the first step in air/lubrication separation. It shall incorporate a means of observing the<br />

lubricant level while the compressor is running, and an ASME coded safety relief valve<br />

of adequate size set at 235 PSIG. Additionally, a lubricant separator with a spin-on<br />

element and service indicator shall be located in the discharge air line for ease in<br />

servicing.<br />

12. Each air compressor shall be equipped with an internal air cooled after cooler and<br />

moisture separator with automatic drain trap. The after cooler shall cool the compressed<br />

air to within about 15-20 degrees F. of the ambient air temperature. Air cooler shall be<br />

Electric-motor-driven, fan-operation, finned-tube unit; rated at 250 psig and leak tested at<br />

350-psig minimum air pressure; in capacities indicated.<br />

13. The compressor assembly shall be mounted on a fabricated steel base.<br />

14. The assembly shall include a sound attenuating enclosure with easily removable side<br />

panels for maximum serviceability.<br />

15. Motor (Each Air Compressor):<br />

a. Horsepower: 40 maximum with a 1.25 maximum service factor.<br />

b. Speed: {Seller selected} rpm.<br />

c. Horizontal, ball bearing, drip proof, C-face, of standard manufacture NEMA<br />

design "B" with class "F" insulation.<br />

d. The motor shall be direct coupled to the compressor for permanent alignment and<br />

incorporate a dry type coupling for minimum maintenance.<br />

e. Efficiency shall meet minimum EPACT requirement.<br />

16. Main Compressor Unit Electrical Characteristics:<br />

a. Volts: 480.<br />

b. Phase(s): Three.<br />

c. Hertz: 60 Hz.<br />

d. Full-Load Amperes: Seller selected .<br />

e. Minimum Circuit Ampacity: Seller selected.<br />

f. Maximum Overcurrent Protection: Seller selected.<br />

17. Electrical Characteristics:<br />

a. Volts: 120 Vac for HP < 1 or 480 Vac for HP > 1.<br />

b. Phase(s): Single Phase for 120 VAC or Three Phase for 480 Vac.<br />

c. Hertz: 60 Hz.<br />

d. Full-Load Amperes: Determined by Seller.<br />

e. Minimum Circuit Ampacity: Determined by Seller.<br />

f. Maximum Overcurrent Protection: Determined by Seller.<br />

18. Capacity Control: Capacity modulation between zero and 100 percent air delivery, with<br />

operating pressures between 50 and 100 psig. Include necessary control to hold constant<br />

pressure. When air demand is zero, unload compressor by using pressure switch and<br />

blowdown valve.<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221519 - 6