01.10.2013 Views

SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

<strong>SECTION</strong> 262913 - ENCLOSED CONTROLLERS<br />

PART 1 - GENERAL<br />

1.1 RELATED DOCUMENTS<br />

A. Drawings and general provisions of the Contract, including General and Supplementary<br />

Conditions and Division 01 Specification Sections, apply to this Section.<br />

1.2 SUMMARY<br />

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:<br />

1. Combination magnetic controllers, full-voltage, non-reversing.<br />

B. Related Sections include the following:<br />

1. Division 26 Section "Variable-Frequency Motor Controllers" for general-purpose, ac,<br />

adjustable-frequency, pulse-width-modulated controllers for use on variable and constant<br />

torque loads in ranges up to 200 hp.<br />

1.3 SUBMITTALS<br />

A. Product Data: Submit manufacturer's technical data for each type of motor controller and<br />

starter, including data proving that materials comply with specified requirements. Provide<br />

catalog sheets showing voltage, controller size, ratings and size of switching and overcurrent<br />

protective devices, short circuit ratings, dimensions, and enclosure details.<br />

B. Wiring Diagrams: Power, signal, and control wiring.<br />

C. Installation instructions: Indicate application conditions and limitations of use stipulated by<br />

Product testing agency specified under Quality Assurance. Include instructions for storage,<br />

handling, protection, examination, preparation, installation, and starting of Product.<br />

D. Operation and maintenance Data: For enclosed controllers to include in operation and<br />

maintenance manuals. In addition to items specified in Division 01 Section "Operation and<br />

Maintenance Data," include the following:<br />

1. Routine maintenance requirements for enclosed controllers and all installed components.<br />

E. Manufacturer Seismic Qualification Certification: Submit certification that enclosed<br />

controllers, accessories, and components will withstand seismic forces defined in Division 26<br />

Section "Vibration and Seismic Controls for Electrical Systems" Include the following:<br />

1. Basis for Certification: Indicate whether withstand certification is based on actual test of<br />

assembled components or on calculation.<br />

a. The term "withstand" means "the unit will remain in place without separation of<br />

any parts from the device when subjected to the seismic forces specified."<br />

Contract 44577 KW Annex – Rev. D 44577-CSI-SPEC-001 262913 - 1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!