Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

c. Stiffen damper blades for stability.<br />

d. Galvanized, roll-formed steel, 0.064 inch thick.<br />

6. Blade Axles: Stainless steel or Nonferrous metal.<br />

7. Bearings: Oil-impregnated bronze or Molded synthetic.<br />

8. Blade Seals: Neoprene.<br />

9. Jamb Seals: Cambered stainless steel.<br />

10. Tie Bars and Brackets: Galvanized steel.<br />

11. Accessories:<br />

a. Include locking device to hold single-blade dampers in a fixed position without<br />

vibration.<br />

2.3 MANUAL VOLUME CONTROL DAMPERS (EXHAUST SYSTEM)<br />

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering<br />

products that may be incorporated into the Work include, but are not limited to, the following:<br />

1. American Warming and Ventilating; a division of Mestek, Inc.<br />

2. Flanders-CSC<br />

3. Greenheck Fan Corporation.<br />

4. Ruskin Company.<br />

B. Dampers shall meet the requirements of ASME AG-1 Section DA “Dampers and Louvers”.<br />

Frame Leakage class (zero leakage) and blade leakage class II (moderate leakage) rating in<br />

accordance with ASME AG-1 Appendix DA-I, with linkage outside the airstream and bearing<br />

AMCA’s Certified Ratings Seal for both air performance and air leakage.<br />

C. Dampers shall be designed for a minimum pressure of minus 20-in w.g.<br />

D. Frames: Steel Channel, material shall be stainless steel Type 304 or 304L and be listed in<br />

ASME AG-1 Table DA-3110.<br />

E. Blades: Fabricated of the same material as the frame, minimum ¼-in. thick.<br />

F. Bearings: Grease lubricated ball bearings mounted outboard of the damper frame.<br />

G. Shaft: Continuous, stainless steel.<br />

H. Shaft seals: external adjustable double packing gland shaft seal.<br />

I. Provide with lockable hand quadrant.<br />

J. Visual Inspection.<br />

1. Perform a Visual Inspection in accordance with ASME AG-1 Section DA-5200 and<br />

Section TA-4220. Submit Visual Inspection procedures and reports.<br />

K. Structural Capability Test:<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 233300 - 4