Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

F. General Description Control Panels: Automatic control station with load control and protection<br />

functions. Comply with NEMA ICS 2 and UL 508.<br />

1. Enclosure: NEMA ICS 6, Type 12 control panel unless otherwise indicated.<br />

2. Motor Controllers: Full-voltage, combination magnetic type with undervoltage release<br />

feature and motor-circuit-protector-type disconnecting means and short-circuit protective<br />

device.<br />

3. Control Voltage: 120-V ac or less, using integral control power transformer.<br />

4. Motor Overload Protection: Overload relay in each phase.<br />

5. Starting Devices: Hand-off-automatic selector switch in cover of control panel, plus pilot<br />

device for automatic control.<br />

6. Instrumentation: Include discharge-air pressure gage, air-filter maintenance indicator,<br />

hour meter, compressor discharge-air and coolant temperature gages, and control<br />

transformer.<br />

7. Alarm Signal Device: For connection to alarm system to indicate compressor trouble.<br />

2.2 OIL-FLOODED, ROTARY-SCREW AIR COMPRESSORS<br />

A. Manufacturers: Subject to compliance with requirements, provide products by one of the<br />

following available manufacturers offering products that may be incorporated into the Work<br />

include, but are not limited to, the following:<br />

B. Basis-of-Design Product: Subject to compliance with requirements contained in Section<br />

012513, Product Substitution Procedures, provide product indicated on Drawings or<br />

comparable product by one of the following:<br />

1. Ingersoll-Rand; Air Solutions Group.<br />

2. Quincy Compressor; an EnPro Industries Company.<br />

3. Rogers Machinery Company.<br />

4. Sullair Corporation.<br />

C. Air Compressor.<br />

1. Compressor Assembly: Single stage, oil-flooded, rotary-screw type with lubricated<br />

helical screws and lubricated gear box.<br />

2. Standard-Air Capacity of Each Air Compressor: 156 scfm minimum free air or 160 acfm<br />

at 660 ft elevation and 68 °F.<br />

3. Discharge-Air Pressure: 135 psig, maximum, 125 psig nominal.<br />

4. Intake-Air Temperature: 68 deg F normal, 95 deg F maximum summer time.<br />

5. The compressor shall have a high efficiency axial inlet. The compressor shall have<br />

tapered roller bearings on the male and female rotor discharge and suction end to contain<br />

axial and radial thrusts. The driven shaft shall be sealed by a triple lip seal arrangement<br />

for long life.<br />

6. Inlet Air Filter: Description: Combination inlet-air filter-silencer, suitable for remote<br />

installation, for each air compressor. Dry type, with maintenance indicator and cleanable<br />

replaceable filter element with silencer tubes or other method of sound reduction. Match<br />

capacity of air compressor, with filter having collection efficiency of 99 percent retention<br />

of particles larger than 10 micrometers.<br />

7. Coupling: Nonlubricated, flexible type and shall include an OSHA type coupling guard.<br />

8. Cooling/Lubrication System: Unit-mounted, air-cooled exchanger package pre-piped to<br />

unit; with air pressure circulation system with coolant stop valve, full-flow<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221519 - 5