Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

B. Maintain temperatures during and after installation of duct sealant.<br />

PART 2 - PRODUCTS<br />

2.1 S<strong>IN</strong>GLE-WALL RECTANGULAR DUCTS AND FITT<strong>IN</strong>GS (SUPPLY, RETURN,<br />

OUTSIDE AIR DUCT)<br />

A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction<br />

Standards - Metal and Flexible" based on 3-inches w.g. static-pressure class, sealing<br />

classification A.<br />

B. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct<br />

Construction Standards - Metal and Flexible," Figure 1-4, "Transverse (Girth) Joints," for staticpressure<br />

class, applicable sealing requirements, materials involved, duct-support intervals, and<br />

other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."<br />

C. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct<br />

Construction Standards - Metal and Flexible," Figure 1-5, "Longitudinal Seams - Rectangular<br />

Ducts," for static-pressure class, applicable sealing requirements, materials involved, ductsupport<br />

intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards -<br />

Metal and Flexible."<br />

D. Elbows, Transitions, Offsets, Branch Connections, and Other Duct Construction: Select types<br />

and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and<br />

Flexible," Chapter 2, "Fittings and Other Construction," for static-pressure class, applicable<br />

sealing requirements, materials involved, duct-support intervals, and other provisions in<br />

SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."<br />

2.2 S<strong>IN</strong>GLE-WALL ROUND DUCTS AND FITT<strong>IN</strong>GS (SUPPLY, RETURN, AND OUTSIDE<br />

AIR DUCTS)<br />

A. General Fabrication Requirements: (Supply, return, and outside air ducts) Comply with<br />

SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 3, "Round,<br />

Oval, and Flexible Duct," based on 3-inches w.g. static-pressure class, Sealing classification A.<br />

B. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct<br />

Construction Standards - Metal and Flexible," Figure 3-2, "Transverse Joints - Round Duct," for<br />

static-pressure class, applicable sealing requirements, materials involved, duct-support intervals,<br />

and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and<br />

Flexible."<br />

C. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct<br />

Construction Standards - Metal and Flexible," Figure 3-1, "Seams - Round Duct and Fittings,"<br />

for static-pressure class, applicable sealing requirements, materials involved, duct-support<br />

intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and<br />

Flexible."<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 233113 - 4