Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

3.10 APPLICABLE PIPE CODES<br />

PIP<strong>IN</strong>G CODE: I-9 Instrument Air Tubing & Piping<br />

Design Pressure 125 psig for Instrument Air<br />

Test Pressure 137 psig for Instrument Air<br />

Operating Temperature<br />

Inspection and Test<br />

Method<br />

Environmental Extremes: -27°F to 110°F<br />

Normal Operating Extremes: 65°F to 80°F (Note 1)<br />

Welded Joints: 5% In-Process Visual Weld Inspection and 100% Final Pass<br />

Visual Weld Inspection<br />

5% Liquid Penetrant Examination of Final Weld Pass<br />

Pneumatic testing at 110% of Design Pressure for all tubing and piping<br />

Sizes 3/4" Tubing and Smaller 1” Pipe and Larger<br />

Tubing/Pipe<br />

Fittings<br />

Stainless Steel Tubing, ASTM A<br />

269, Grade TP304L or TP316L,<br />

fully annealed (90 HRb or less)<br />

seamless tubing. Minimum wall<br />

thickness 0.035” for ½” OD and<br />

smaller, 0.065” for greater than ½”<br />

OD. Tubing must be suitable for<br />

bending and surface scratches or<br />

other imperfections are not permissible.<br />

Welded Joints: ASTM A 182/A<br />

182M seamless fittings matching<br />

tube thickness and grade<br />

Mechanical Joints: Type 304L or<br />

316L SST Flareless type, "Swagelok",<br />

"Parker" or approved equal.<br />

Staubli HCB28 series, size and<br />

type as specified on the fabrication<br />

drawings.<br />

Stainless Steel Pipe, Schedule 40,<br />

ASTM A 312/ A312M, Grade TP304L<br />

or TP316L, seamless<br />

ASTM A 403/A 403M, Class S 304L,<br />

wall thickness and grade to match<br />

pipe.<br />

Valves Stainless steel, Type 316, per ASME B16.34 or as shown on Drawings.<br />

Note:<br />

1) Based on 65°F winter and 80°F summer inside HVAC design temperatures.<br />

2) Standards referenced above shall be used unless approved by the Buyer.<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221513 - 30