01.10.2013 Views

SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

2. Perform a final visual examination of all pressure boundary welds including attachment<br />

welds (not just the 5% specified by ASME B31.3) in accordance with ASME B31.3, paragraph<br />

341.4.1 and 344.2.<br />

3. Liquid penetrant examine the final weld surface of all socket welds, slip on flange welds,<br />

branch connection welds (5% specified by ASME B31.3) and 5% of all circumferential<br />

butt welds (final pass) in accordance with ASME B31.3, paragraph 344.4.<br />

4. If a random examination reveals a defect, the requirements of ASME B31.3, paragraph<br />

341.3.4, Progressive Examination, apply.<br />

5. Perform examinations to written procedures in accordance with ASME B31.3, paragraph<br />

343.<br />

6. The acceptance criteria of ASME B31.3, paragraph 341.4.1, and Table 341.3.2 apply for<br />

visual examination with the exception that incomplete penetration for complete penetration<br />

welds is unacceptable.<br />

7. The acceptance criteria for liquid-penetrant examination follows:<br />

a. Relevant indications are those with major dimensions greater than 1/16 in.<br />

b. The following relevant indications are unacceptable:<br />

i. cracks;<br />

ii. linear indication (indication whose length is more than three times its width);<br />

iii. rounded indications with dimensions greater than 1/8 in.;<br />

iv. four or more rounded indications in a line separated by 1/16 in. or less edge<br />

to edge; and<br />

v. ten or more rounded indications in any 6 sq. in. of surface area with the<br />

major dimension of this area not to exceed 6 in. and with the area taken in the<br />

most unfavorable location relative to the indications being evaluated.<br />

8. Perform the Pressure – Leak test of the completed piping sections in accordance with<br />

ASME B31.3, paragraph 345.<br />

H. Installer Qualifications:<br />

1. Pressure-Seal Joining Procedure for Stainless Steel tube fitting. Qualify operators<br />

according to training provided by Swagelok Company.<br />

I. ASME Compliance:<br />

1. Comply with ASME B31.3, "Process Piping," Normal Service Category, for IXM piping.<br />

Contract 44577 KW Annex – Rev E. 44577-CSI-SPEC-001 402319-5