Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

7. Proof Pressure Test per RMA IP-2 and ASTM D 380 (sections 14, 15 and 17), test pressure<br />

shall be 50% of the minimum specified burst pressure, held for a minimum of 10<br />

minutes.<br />

B. Basis-of-Design Product: Subject to compliance with requirements contained in Section<br />

012513, Product Substitution Procedures, provide the product indicated on Drawings or a<br />

comparable product, approved by the Buyer, by one of the following:<br />

1. Flex-Hose Co., Inc.<br />

2. Flexicraft (Hosecraft Industries, Inc).<br />

3. Hosexpress<br />

4. Hyspan Precision Products, Inc.<br />

5. Mercer Rubber Co.<br />

6. Metraflex, Inc.<br />

7. Proco Products, Inc.<br />

8. Pureflex, Inc.<br />

9. River Bend Hose Specialty.<br />

10. Swagelok Industries, Inc.<br />

11. Unaflex, Inc.<br />

12. US Hose Corp.<br />

2.4 BALL VALVES<br />

A. Description; Ball Valves, NPS 3 and Smaller:<br />

1. Standard: MSS SP-72, or MSS SP-110, and ASME B 16.34,<br />

2. Pressure Rating: Class 150,<br />

3. Body Design: 3 piece,<br />

4. Body/End Cap Material: stainless-steel, ASTM A 351 Grade CF8M,<br />

5. Port: full-port<br />

6. Ball: stainless-steel,<br />

7. Stem: stainless-steel,<br />

Contract 44577 KW Annex – Rev E. 44577-CSI-SPEC-001 402319-12