Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

Hardware Points Software Points<br />

Point Name AI AO BI BO AV BV Sched Trend Alarm<br />

Fire Alarm Control Panel Signal x x<br />

Building Exhaust Air Flow Setpoint<br />

Show On<br />

Graphic<br />

× × ×<br />

High Building Exhaust Air Flow ×<br />

Low Building Exhaust Air Flow ×<br />

Fan Failure ×<br />

Fan in Hand ×<br />

Fan Runtime Exceeded ×<br />

ECRT-HEPA-501 High DP x<br />

ECRT-HEPA-501 Low DP x<br />

ECRT-HEPA-502 High DP x<br />

ECRT-HEPA-501 Low DP x<br />

Totals 1 1 3 1 1 0 0 5 11 6<br />

1.5 ECRT-AHU-501<br />

Total Hardware ( 6 ) Total Software ( 13 )<br />

A. Run Conditions - Continuous:<br />

1. The unit shall be interlocked with ECRT-EF-501 and ECRT-EF-502 and shall not<br />

operate if both exhaust fans are inoperable, and shall maintain:<br />

a. A 80°F (adj.) cooling setpoint<br />

b. A 65°F (adj.) heating setpoint.<br />

B. Control - Building Supply Air Flow:<br />

1. The supply fan shall run when commanded on.<br />

2. The controller shall measure building sludge loading bay supply air flow and modulate<br />

the supply fan VFD speed to maintain an offset air flow between the Exhaust Air Flow<br />

and the Supply Air Flow, offset setpoint of 1,135 cfm (adj.) (4,100 cfm exhaust flow –<br />

2,965 cfm Sludge Loading bay supply flow). The supply fan VFD speed shall not drop<br />

below 20% (adj.).<br />

C. Alarms shall be provided as follows:<br />

1. High Building supply air flow: If the building supply air flow is 25% (adj.) greater than<br />

setpoint.<br />

2. Low Building supply air flow: If the building supply air flow is 25% (adj.) less than<br />

setpoint.<br />

3. High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user<br />

definable amount (adj.).<br />

4. Low Zone Temp: If the zone temperature is less than the heating setpoint by a user<br />

definable amount (adj.).<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230993 - 3