Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

<strong>SECTION</strong> 221519 - GENERAL-SERVICE PACKAGED AIR COMPRESSORS AND RECEIVERS<br />

PART 1 - GENERAL<br />

1.1 RELATED DOCUMENTS<br />

A. Drawings and general provisions of the Contract, including General and Supplementary<br />

Conditions and Division 01 Specification Sections, apply to this Section.<br />

1.2 SUMMARY<br />

A. Section Includes:<br />

1. Oil-flooded, rotary-screw air compressors.<br />

2. Inlet-air filters.<br />

3. Air-cooled, compressed-air after coolers.<br />

4. Desiccant compressed-air dryers.<br />

5. Air Receiver Tanks.<br />

6. Computer interface cabinet.<br />

1.3 SUBMITTALS<br />

A. Submittals shall be in accordance with Section 013300, Submittals.<br />

B. Product Data: For each type of product indicated. Include rated capacities, operating<br />

characteristics, electrical characteristics, and furnished specialties and accessories.<br />

1. Complete performance data shall accompany proposal and shall include capacity in<br />

ACFM at the compressor inlet and at delivery pressure of 120 PSIG and at maximum<br />

pressure capability, brake horsepower at full load conditions, rotor speed, cooling air<br />

flow, and all other pertinent data.<br />

2. Completed Data Sheets in accordance with ISA20.<br />

3. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate<br />

and describe mounting and anchorage provisions.<br />

4. Wiring Diagrams: For power, signal, and control wiring.<br />

5. Completed MSDSs for all lubricants and chemicals.<br />

C. Seismic Qualification Certificates: For compressed-air equipment, accessories, and<br />

components, from manufacturers.<br />

1. Basis for Certification: Indicate whether withstand certification is based on actual test of<br />

assembled components or on calculation.<br />

2. Detailed description of equipment anchorage devices on which the certification is based<br />

and their installation requirements.<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221519 - 1