1. UL-Classified Systems: W-L- 4001-4999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

L. Firestopping for Insulated Pipes located in Concrete Walls:<br />

1. UL-Classified Systems: C-AJ- 5001-5999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

M. Firestopping for Insulated Pipes located in GWB Walls:<br />

1. UL-Classified Systems: W-L- 5001-5999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

N. Firestopping for Miscellaneous Electrical Penetrants located in Concrete Walls:<br />

1. UL-Classified Systems: C-AJ- 6001-6999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

O. Firestopping for Miscellaneous Electrical Penetrants located in GWB Walls:<br />

1. UL-Classified Systems: W-L- 6001-6999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

P. Firestopping for Miscellaneous Mechanical Penetrants located in Concrete Walls:<br />

1. UL-Classified Systems: C-AJ- 7001-7999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

Q. Firestopping for Miscellaneous Mechanical Penetrants located in GWB Walls:<br />

1. UL-Classified Systems: W-L- 7001-7999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

R. Firestopping for Groupings of Penetrants located in Concrete Walls:<br />

1. UL-Classified Systems: C-AJ- 8001-8999.<br />

2. F-Rating: 2 hours.<br />

3. Type of Fill Materials: As required to achieve rating.<br />

S. Firestopping for Groupings of Penetrants located in GWB Walls:<br />

1. UL-Classified Systems: W-L- 8001-8999.<br />

2. F-Rating: 2 hours.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 078413 - 8