Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

40. Heater elements mounted externally shall not come into direct contact with desiccant bed.<br />

This design minimizes thermal shock, scorching and premature aging of desiccant caused<br />

by internally mounted heater elements.<br />

41. Heater shall be sized for complete regeneration air requirement. To maximize heater<br />

element service life, the heater shall be operated by a solid state relay with a set<br />

temperature of 375 deg F. Heater watt density shall not exceed 23 watts per square inch.<br />

The heater shall be Incoloy sheathed and insulated.<br />

42. Externally mounted heater design shall reduce the potential for a compressed air line fire<br />

common to internal heater-type designs. Heater assembly shall include direct monitoring<br />

of the heater housing. A thermocouple shall measure the internal heater housing<br />

temperature and shut-down the heater upon High Heater Temperature condition.<br />

Interlock shall be included to prevent heater from re-energizing without being manually<br />

reset.<br />

43. A temperature gauge mounted on each dryer tower shall act as a visual indicator that<br />

tower regeneration is occurring.<br />

44. All electrical equipment and components shall conform to the latest edition of the<br />

National Electrical Code (NEC) and the National Electrical Manufacturers Association<br />

(NEMA).<br />

45. Drying system shall be designed so that single entry, 480V/3PH/60HZ electrical power<br />

can be brought into control enclosure.<br />

46. Electrical Characteristics:<br />

a. Volts: 480 Vac.<br />

b. Phase(s): Three.<br />

c. Hertz: 60 Hz.<br />

d. Full-Load Amperes: Determined by Seller.<br />

e. Minimum Circuit Ampacity: Determined by Seller.<br />

f. Maximum Overcurrent Protection: Determined by Seller.<br />

2.5 COMPUTER <strong>IN</strong>TERFACE CAB<strong>IN</strong>ET<br />

A. Description:<br />

1. Wall mounting.<br />

2. Welded steel with white enamel finish.<br />

3. Gasketed door.<br />

4. Grounding device.<br />

5. Factory-installed, signal circuit boards.<br />

6. Power transformer.<br />

7. Circuit breaker.<br />

8. Wiring terminal board.<br />

9. Internal wiring capable of interfacing 5 alarm signals.<br />

2.6 MOTORS<br />

A. Comply with NEMA designation, temperature rating, service factor, enclosure type, and<br />

efficiency requirements for motors specified in Division 23 Section 230513 "Common Motor<br />

Requirements for HVAC Equipment."<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221519 - 10