Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

D. Zone Setpoint Adjust:<br />

1. The occupant shall be able to adjust the zone temperature heating and cooling setpoints at<br />

the zone sensor.<br />

E. Supply Air Smoke Detection:<br />

1. The unit shall shut down and generate an alarm upon receiving a supply air smoke<br />

detector status.<br />

F. Fire Alarm Signal:<br />

1. The unit shall shut down and generate an alarm upon receiving a signal from the fire<br />

alarm control panel. The fire alarm signal shall override all other signals and shut down<br />

the unit.<br />

G. Supply Fan:<br />

1. The supply fan shall run anytime the unit is commanded to run, unless shutdown on<br />

safeties.<br />

2. Alarms shall be provided as follows:<br />

a. Supply Fan Failure: Commanded on, but the status is off.<br />

b. Supply Fan in Hand: Commanded off, but the status is on.<br />

c. Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit<br />

(adj.).<br />

d. Supply Fan VFD fault<br />

H. Cooling Coil Valve:<br />

1. The controller shall measure the zone temperature and modulate the cooling coil valve to<br />

maintain its cooling setpoint.<br />

2. The cooling shall be enabled whenever:<br />

a. Outside air temperature is greater than 55°F (adj.).<br />

b. AND the zone temperature is above cooling setpoint.<br />

c. AND the supply fan status is on.<br />

d. AND the heating is not active.<br />

I. Heating Coil Valve (the same valve as the cooling coil valve):<br />

1. The controller shall measure the zone temperature and modulate the heating coil valve to<br />

maintain its heating setpoint.<br />

2. The heating shall be enabled whenever:<br />

a. Outside air temperature is less than 50°F (adj.).<br />

b. AND the zone temperature is below heating setpoint.<br />

c. AND the supply fan status is on.<br />

d. AND the cooling is not active.<br />

J. Mixed Air Dampers:<br />

1. The mixed air dampers shall open to provide minimum outside air ventilation anytime the<br />

unit is occupied. The mixed air dampers shall close 5 sec (adj.) after the supply fan stops,<br />

the outside air bypass damper shall open if either ECRT-EF-501 or ECRT-EF-502 are<br />

operating.<br />

2. If Optimal Start Up is available, the outside air damper shall close and the return air<br />

damper shall open.<br />

3. Minimum Outside Air Ventilation - Fixed Percentage:<br />

The outside air dampers shall maintain a minimum position (adj.).<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230993 - 4