Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

Valves<br />

3 x pipe nominal outside diameter.<br />

Mechanical Joints: 304L or 316L<br />

SST Flareless type, “Crawford”,<br />

"Swagelok", "Parker" or approved<br />

equal in accordance with ASTM A<br />

182/A 182M A 276 or SA 479.<br />

ASME B16.34, stainless steel body, stainless steel ball with fractional<br />

tube ends, UHMWPE seats. Manual locking handle.<br />

Note:<br />

1) Based on 65 °F winter and 80 °F summer inside HVAC design temperatures.<br />

2) Standards referenced above shall be used unless approved by buyer.<br />

Design Pressure 100 psig<br />

PIP<strong>IN</strong>G CODE H-1: Hoses<br />

Test Pressure 50% of the minimum specified burst pressure<br />

Operating Temperature<br />

Sizes 1/4" NPS and larger<br />

Environmental Extremes: -27°F to 110°F for outside applications<br />

Normal Operating Extremes: 65°F to 80°F (Note 1)<br />

Hose RMA IP-2, Hose Handbook, ASTM D 380<br />

Fittings<br />

Autolok TM quick couplings, made by the OPW Company, 300 Series SST,<br />

Threaded or Welded as specified on fabrication drawings. Size and type as<br />

specified on the fabrication drawings.<br />

Campbell Chemjoint TM size and type as specified on the fabrication drawings.<br />

River Bend Hose Fittings, size and type as specified on the fabrication drawings.<br />

Staubli HCB28 series, size and type as specified on the fabrication drawings.<br />

Swagelok, size and type as specified on the fabrication drawings.<br />

Note:<br />

1) Based on 65°F winter and 80°F summer inside HVAC design temperatures.<br />

2) Standards referenced above shall be used unless approved by buyer.<br />

3) AUTOLOK is a registered trademark of Delaware Capital Formation, Inc., Wilmington, Delaware.<br />

4) Chemjoint is a registered trademark of Campbell Fittings, Inc., Boyertown Pennsylvania.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 226313 - 32

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!