Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

cimen does not exceed corrosion rate of any of the previous specimens by more than<br />

0.0002 in. per month.<br />

E. Wrought Forged-Steel Flanges and Flanged Fittings: ASME B16.5, including bolts, nuts, and<br />

gaskets of the following material group, end connections, and facings:<br />

1. Material Group: 2.3.<br />

2. End Connections: Weld Neck - Butt welding.<br />

3. Facings: Raised face.<br />

2.2 STRUCTURAL MATERIALS<br />

A. Carbon steel shall meet the requirements of ASTM A 36/A 36M or ASTM A 992/A 992M.<br />

B. Structural tubing shall meet the requirements of ASTM A 500/A 500M, Grade B (fy = 46 ksi).<br />

C. Steel pipe shall meet the requirements of ASTM A 53/A 53M, black steel, Type E or S, Grade B,<br />

or ASTM A 106/A 106M, Grade B, standard weight, Schedule 40 and Schedule 80.<br />

D. Concrete expansion anchors shall be any industry standard wedge-type expansion anchor having<br />

capacities published by the ICC-ES and approved for resistance to wind and seismic loading.<br />

E. All exposed carbon steel shall be coated in accordance with Section 055000, Metal Fabrications.<br />

Prepare, prime, and top coat structural steel in accordance with the manufacturer’s recommendations.<br />

The final coat shall be light gray. All coatings shall be applied in such a manner as to produce<br />

a uniform smoothness. Special attention shall be paid to crevices, weld lines, carriers, and<br />

edges to obtain the required thickness.<br />

2.3 STA<strong>IN</strong>LESS-STEEL BRAIDED PTFE HOSE (1” AND SMALLER)<br />

A. Flex Line: Silicone-covered PTFE hose with stainless-steel wire-braid covering.<br />

1. Cover: Stainless steel, wire-reinforcing protective jacket.<br />

2. Core: Silicone-covered PTFE hose with fiber braid bonded to the core.<br />

3. End Connections: As Scheduled on Drawings.<br />

4. CWP Rating: 200 psig, minimum.<br />

5. Operating Temperature: 100 deg F, maximum.<br />

6. Leak Test per RMA IP-2 and ASTM D 380 (sections 14.2 and 15.2), test pressure shall<br />

be 10 to 15 psig, held for a minimum of 10 minutes.<br />

7. Proof Pressure Test per RMA IP-2 and ASTM D 380 (sections 14, 15 and 17), test pressure<br />

shall be 50% of the minimum specified burst pressure, held for a minimum of 10<br />

minutes.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 226313 - 12