Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

F. Specifications: include compliance information with The National (DOE) Efficiency Standard,<br />

and any exceptions taken, prior to manufacturing.<br />

G. Material Safety Data Sheet (MSDS) for insulating fluid.<br />

H. Operation and Maintenance Data: Installation instruction manual and maintenance instruction<br />

manuals.<br />

1.5 QUALITY ASSURANCE<br />

A. Testing Agency Qualifications: An independent testing agency, with the experience and<br />

capability to conduct the testing indicated, that is a member company of the InterNational<br />

Electrical Testing Association or is a nationally recognized testing laboratory (NRTL) as<br />

defined by OSHA in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.<br />

1. Testing Agency's Field Supervisor: Person currently certified by the InterNational<br />

Electrical Testing Association or the National Institute for Certification in Engineering<br />

Technologies to supervise on-site testing specified in Part 3.<br />

B. Product Options: Drawings indicate size, profiles, and dimensional requirements of<br />

transformers and are based on the specific system indicated. Refer to Division 01 Section<br />

"Product Requirements."<br />

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,<br />

Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for<br />

intended use.<br />

D. Comply with IEEE C2.<br />

E. Comply with ANSI C57.12.10, ANSI C57.12.28, IEEE C57.12.70, and IEEE C57.12.80.<br />

F. Comply with NFPA 70.<br />

G. Perform testing in accordance with ANSI C57.12.00, Section 8.<br />

1.6 DELIVERY, STORAGE, AND HANDL<strong>IN</strong>G<br />

A. Packaging shall be of such to eliminate ingress of water and other contaminants. Items that<br />

could be damaged during shipment shall be removed and placed in separate packing. If left<br />

attached, items are to be protected.<br />

B. Handle using lifting eyes provided. Keep transformer in upright position.<br />

1.7 PROJECT CONDITIONS<br />

A. Service Conditions: IEEE C37.121, usual service conditions except for the following:<br />

1. Exposure to significant solar radiation.<br />

Contract 44577 KW Annex – Rev. D 44577-CSI-SPEC-001 261200 - 2