Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

Hardware Points Software Points<br />

Point Name AI AO BI BO AV BV Sched Trend Alarm Show On Graphic<br />

High Zone Temp ×<br />

Low Zone Temp ×<br />

Filter Change Required ×<br />

Fan Failure ×<br />

Fan in Hand ×<br />

Fan Runtime Exceeded ×<br />

1.10 ECRT-HP-501<br />

Totals 3 1 2 1 2 0 1 9 6 9<br />

Total Hardware ( 7 ) Total Software ( 18 )<br />

A. Chiller Heat Pump - Run Conditions:<br />

1. The chiller shall be enabled to run whenever it is commanded to be enabled by the chiller<br />

manager program. The chiller shall run subject to its own internal safeties and controls.<br />

2. The controls contractor shall coordinate with the chiller manufacturer to disable the<br />

chiller whenever the ambient temperature drops below or rises above the manufacturer’s<br />

written recommended operating temperatures. The heat pump water pump shall be<br />

interlocked to turn off when the chiller is commanded off.<br />

B. Heat Pump Water Pump (ECRT-P-502):<br />

1. The heat pump water pump shall run anytime the heat pump chiller is called to run.<br />

2. The heat pump water pump shall start prior to the heat pump chiller being enabled and<br />

shall stop only after the heat pump chiller is disabled. The heat pump water pump shall<br />

therefore have:<br />

a. A user adjustable delay on start.<br />

b. AND a user adjustable delay on stop.<br />

3. The delay times shall be set appropriately to allow for orderly hydronic water system<br />

start-up, shutdown and sequencing.<br />

4. Alarms shall be provided as follows:<br />

a. Heat Pump Water Pump Failure: Commanded on, but the status is off.<br />

b. Heat Pump Water Pump Running in Hand: Commanded off, but the status is on.<br />

c. Heat Pump Water Pump Runtime Exceeded: Status runtime exceeds a user<br />

definable limit.<br />

C. Heat Pump Chiller:<br />

1. The heat pump chiller shall be enabled a user adjustable time after pump statuses are<br />

proven on. The heat pump chiller shall therefore have a user adjustable delay on start.<br />

2. The delay time shall be set appropriately to allow for orderly hydronic water system startup,<br />

shutdown and sequencing.<br />

3. The heat pump chiller shall run subject to its own internal safeties and controls.<br />

4. Alarms shall be provided as follows:<br />

a. Heat Pump Chiller Failure: Commanded on, but the status is off.<br />

b. Heat Pump Chiller Running in Hand: Commanded off, but the status is on.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230993 - 13