01.10.2013 Views

SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SECTION 033000 - CAST-IN-PLACE CONCRETE

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

B. Protect bearings and couplings against damage.<br />

C. Comply with pump manufacturer's written rigging instructions for handling.<br />

1.6 COORD<strong>IN</strong>ATION<br />

A. Coordinate size and location of pits.<br />

PART 2 - PRODUCTS<br />

2.1 MANUFACTURERS<br />

A. The station manufacturer shall be required to affix an UNDERWRITER’S LABORATORIES<br />

(UL) LABEL attesting to the compliance of that assembled equipment under the PACKAGED<br />

PUMP SYSTEMS (QCZJ) UL Listing Category This label shall be inclusive of the entire<br />

station with enclosure so as to demonstrate compliance with the National Electrical Code<br />

requirements for working clearances and wiring procedures.<br />

B. In other Part 2 articles where titles below introduce lists, the following requirements apply to<br />

product selection:<br />

1. Available Manufacturers: Subject to compliance with requirements, manufacturers<br />

offering products that may be incorporated into the Work include, but are not limited to,<br />

manufacturers specified.<br />

a. PumpTech, Inc.<br />

b. Flygt; ITT Industries.<br />

2.2 SUBMERSIBLE, QUICK-DISCONNECT SEWAGE PUMPS:<br />

A. Factory-assembled and -tested, duplex, single-stage, centrifugal, end-suction, submersible,<br />

direct-connected sewage pumps complying with UL 778 and with HI 1.1-1.2 and HI 1.3 for<br />

submersible sewage pumps and with SWPA's "Submersible Sewage Pumping Systems (SWPA)<br />

Handbook" for guide-rail supports. Include reverse-flow assembly.<br />

1. Available Manufacturers:<br />

a. Flygt; ITT Industries.<br />

b. ABS Inc.<br />

2. Casing: Cast iron (ASTM A-48, Class 35B), with open inlet, legs (or guide-rail supports)<br />

that elevate pump to permit flow into impeller, and vertical discharge with companion<br />

flange for piping connection. All metal surfaces coming into contact with the pumped<br />

media except stainless steel components shall have protective spray coating. Housing<br />

design shall incorporate metal-to-metal contact between machined surfaces. Surfaces<br />

where watertight sealing is required shall be machined and fitted with Nitrile or Viton<br />

rubber O-rings.<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221329-2