Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

1. All Pipe Sizes: Insulation shall be the following:<br />

a. Mineral-Fiber, Preformed Pipe, Type I or II: 1 inch thick.<br />

D. Hot Service Vents:<br />

1. All Pipe Sizes: Insulation shall be the following:<br />

a. Mineral-Fiber, Preformed Pipe, Type I or II: 1 inch thick.<br />

3.16 OUTDOOR, ABOVEGROUND PIP<strong>IN</strong>G <strong>IN</strong>SULATION SCHEDULE<br />

A. Hydronic Water:<br />

1. All Pipe Sizes: Insulation shall be the following:<br />

a. Mineral-Fiber, Preformed Pipe Insulation, Type I: 3 inches thick.<br />

3.17 <strong>IN</strong>DOOR, FIELD-APPLIED JACKET SCHEDULE<br />

A. Install jacket over insulation material. For insulation with factory-applied jacket, install the<br />

field-applied jacket over the factory-applied jacket.<br />

B. If more than one material is listed, selection from materials listed is Contractor's option.<br />

C. Ducts and Plenums, Concealed: None.<br />

D. Ducts and Plenums, Exposed: None.<br />

E. Piping, Concealed: None.<br />

F. Piping, Exposed below 8 ft above the finished floor, except flexible elastomeric insulation:<br />

Stainless Steel, Type 304 Smooth 2B Finish: 0.016 inch thick.<br />

3.18 OUTDOOR, FIELD-APPLIED JACKET SCHEDULE<br />

A. Install jacket over insulation material. For insulation with factory-applied jacket, install the<br />

field-applied jacket over the factory-applied jacket.<br />

B. If more than one material is listed, selection from materials listed is Contractor's option.<br />

C. Piping, Exposed:<br />

1. Stainless Steel, Type 304, Stucco Embossed with Z-Shaped Locking Seam: 0.016 inch<br />

thick.<br />

END OF <strong>SECTION</strong> 230700<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230700 - 21