D. Tees and Laterals: Select types and fabricate according to SMACNA's "HVAC Duct<br />

Construction Standards - Metal and Flexible," Figure 3-4, "90 Degree Tees and Laterals," and<br />

Figure 3-5, "Conical Tees," for static-pressure class, applicable sealing requirements, materials<br />

involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct<br />

Construction Standards - Metal and Flexible."<br />

2.3 DUCTWORK FABRICATION - EXHAUST DUCTWORK<br />

A. Fabricate process area exhaust ductwork and supports in accordance with ASME AG-1, Article<br />

SA, Service Level C, and Table SA-C-1300, SMACNA Round Industrial Duct Construction<br />

Standards, Class 1, and SMACNA Rectangular Industrial Duct Construction Standards, Class 1.<br />

Pressure Classification negative 20-in water gauge, including maintenance load. Fabricate<br />

seismic bracing in accordance with Division 23, Section “Vibration and Seismic Controls for<br />

HVAC, Piping and Equipment”.<br />

B. Construct bends, and elbows with minimum radius 1-1/2 times centerline duct width. Where<br />

not possible and where rectangular elbows are used, provide single thickness turning vanes<br />

constructed and installed in accordance with SMACNA Standards.<br />

C. Provide, at minimum, rectangular 45 degree entry fittings for rectangular ducts and 45 degree<br />

wye takeoffs for round ducts, unless shown otherwise on drawings.<br />

D. Duct sizes noted are inside clear dimensions.<br />

E. Increase duct size gradually, not exceeding 15 degree divergence wherever possible. Do not<br />

exceed 30-degree divergence upstream of equipment. Do not exceed 45-degree convergence<br />

downstream of equipment.<br />

2.4 SHEET METAL MATERIALS<br />

A. General Material Requirements: Comply with SMACNA's "HVAC Duct Construction<br />

Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct<br />

construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting,<br />

seam marks, roller marks, stains, discolorations, and other imperfections.<br />

B. Galvanized Sheet Steel: (Supply, Return, and Outside Air ductwork) Comply with<br />

ASTM A 653/A 653M.<br />

1. Galvanized Coating Designation: G90.<br />

2. Finishes for Surfaces Exposed to View: Mill phosphatized.<br />

C. Stainless-Steel Sheets: (Exhaust system ductwork) Comply with ASTM A 240/A 240M or<br />

A 480/A 480M, Type 304 or 304L, as indicated in the "Duct Schedule" Article; cold rolled,<br />

annealed, sheet. Exposed surface finish shall be No. 2B. Submit material test reports.<br />

D. Factory- or Shop-Applied Antimicrobial Coating:<br />

1. Apply to the surface of sheet metal that will form the interior surface of the duct. An<br />

untreated clear coating shall be applied to the exterior surface.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 233113 - 5