Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

13. Weld Filler Material(s) (WFM): The material (metal and nonmetal) to be added when<br />

making a weld, braze or bond joint<br />

14. Weld Maps: Formal sketches, design drawings, or shop drawings that show the location<br />

of welds in a system, so that documentation (i.e., Certified Material Test Reports, Welder<br />

Identification, and Weld Examination Records) can be traced to the weld it represents.<br />

15. Welder Performance Qualification (WPQ): The record which documents a Welder's successful<br />

completion of a performance qualification test and establishes the range of variables<br />

the Welder is qualified for.<br />

16. Welding Procedure Specification (WPS): a document providing in detail the required variables<br />

for a specific welding application to assure repeatability by properly trained welders<br />

and welding operators<br />

17. Work Package (WP): Consists of a collection of forms, documents, procedures, work instructions,<br />

etc. necessary to support a certain scope of work.<br />

18. WQ&I: Welder Qualification and Inspection<br />

1.6 PERFORMANCE REQUIREMENTS<br />

A. General Conditions for the General Service Compressed Air Piping system:<br />

1. Compressed air system: Normal operating pressure at 135 psig, maximum.<br />

2. Compressed air system: Normal design pressure of 150 psig.<br />

3. Instrument air system: Normal operating pressure at 100 psig, maximum.<br />

4. Instrument air system: Normal design pressure of 125 psig.<br />

5. Normal minimum operating temperature at 65 deg F.<br />

6. Normal maximum operating temperature at 80 deg F.<br />

7. Fluid properties are the same as clean air at 68 deg F.<br />

8. Piping Code: ASME B31.3, Normal Service.<br />

B. Manufacturer Seismic Qualification Certification: Submit certification that General Service<br />

Compressed Air Piping, accessories, and components will withstand seismic forces defined in<br />

Section 220548, Vibration and Seismic Controls for Plumbing Piping and Equipment. Include<br />

the following:<br />

1. The term "withstand" means "the unit will remain in place without separation of any parts<br />

from the device when subjected to the seismic forces specified."<br />

2. Basis for Certification: Indicate whether withstand certification is based on actual test of<br />

assembled components or on calculation.<br />