Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

<strong>SECTION</strong> 331116 - FACILITY WATER DISTRIBUTION PIP<strong>IN</strong>G<br />

PART 1 - GENERAL<br />

1.1 SUMMARY<br />

A. This Section includes water-distribution piping and related components outside the building for<br />

fire-service mains.<br />

1.2 SUBMITTALS<br />

A. Product Data: For each type of product indicated.<br />

B. Field quality-control and pressure test reports.<br />

C. Cleaning reports.<br />

D. Operation and maintenance data.<br />

1.3 QUALITY ASSURANCE<br />

A. Regulatory Requirements:<br />

1. Comply with standards of authorities having jurisdiction for fire-suppression waterservice<br />

piping, including materials, hose threads, installation, and testing.<br />

B. Piping materials shall bear label, stamp, or other markings of specified testing agency.<br />

C. Comply with FMG's “Approval Guide” or UL's “Fire Protection Equipment Directory” for fireservice-main<br />

products.<br />

D. NFPA Compliance: Comply with NFPA 24 for materials, installations, tests, flushing, and<br />

valve and hydrant supervision for fire-service-main piping for fire suppression.<br />

1.4 PROJECT CONDITIONS<br />

A. Interruption of Existing Water-Distribution Service: Do not interrupt service to facilities<br />

occupied by Owner or others unless permitted under the following conditions:<br />

1. Notify the Buyer’s Technical Representative no fewer than five (5) days in advance of<br />

proposed interruption of service.<br />

2. Do not proceed with interruption of water-distribution service without written permission<br />

from Buyer’s Technical Representative.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 331116 - 1