Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

1. Perform a Structural Capability test of each completed damper assembly to minus 15.0<br />

in. w.g in accordance with ASME AG-1 Section DA-5500, Section TA-4231, and Section<br />

TA-4232 on the completed damper frame and blade prior to the final pressure decay leak<br />

test. Submit certifications of the Structural Capability test.<br />

L. Pressure Decay Leak Test:<br />

1. Factory leak test each completed damper assembly to minus 12.5 in. w.g. in accordance<br />

with ASME AG-1 Section DA-5130, Section DA-5141, Section TA-4233, Section TA-<br />

4234, and Section TA-4235. Frame leak test acceptance criteria, damper shall be leakage<br />

class (zero leakage) and seat leakage acceptance criteria shall be Leakage Class II at<br />

design pressure in accordance with ASME AG-1 Appendix DA-I. Rectify and retest any<br />

deficiency and work affected by such deficiency.<br />

M. Submit Seat leakage, frame leakage, and pressure drop ratings in accordance with ASME AG-1<br />

Section DA-4130.<br />

N. Submit documentation required by ASME AG-1 subsection DA-4212.2<br />

O. Submit certifications of materials in accordance with ASME AG-1 Section DA-3300.<br />

2.4 CONTROL DAMPERS<br />

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering<br />

products that may be incorporated into the Work include, but are not limited to, the following:<br />

1. American Warming and Ventilating; a division of Mestek, Inc.<br />

2. Greenheck Fan Corporation.<br />

3. McGill AirFlow LLC.<br />

4. METALAIRE, Inc.<br />

5. Nailor Industries Inc.<br />

6. Ruskin Company.<br />

B. Low-leakage rating, with linkage outside airstream, and bearing AMCA's Certified Ratings Seal<br />

for both air performance and air leakage.<br />

C. Frames:<br />

1. Hat Channel shaped.<br />

2. Galvanized-steel channels, 0.064 inch thick.<br />

3. Mitered and welded corners.<br />

D. Blades:<br />

1. Multiple blade with maximum blade width of 8 inches.<br />

2. Parallel blade design.<br />

3. Galvanized steel.<br />

4. 0.064 inch thick.<br />

5. Blade Edging: PVC coated polyester locked into blade edge.<br />

6. Jamb Seals: Flexible metal compression type.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 233300 - 5