Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

E. Capacities and Characteristics:<br />

1. System Capacity: 2,000 gpm<br />

2. Number of Pumps: Two.<br />

3. Each Pump:<br />

a. Capacity: 1,000 gpm.<br />

b. Solids Handling Capability: 3 inches minimum.<br />

c. Total Dynamic Head: 40 feet.<br />

d. Speed: 1,185 rpm<br />

e. Discharge Pipe Size: 8” NPS.<br />

f. Motor Horsepower: 30 hp<br />

g. Electrical Characteristics:<br />

1) Volts: 480.<br />

2) Phases: Three.<br />

3) Hertz: 60.<br />

h. Unit Electrical Characteristics:<br />

1) Full-Load Amperes: 35 Amps<br />

4. Alternator Control Required: Yes.<br />

5. Guide-Rail Supports Required: Yes.<br />

2.3 SEWAGE PUMP BAS<strong>IN</strong>S<br />

A. Description: Factory fabricated basin with sump, pipe connections, and separate cover.<br />

B. Sump: Fabricate watertight, with sidewall openings for pipe connections.<br />

1. Material: Fiberglass wet well and integral valve vault shall be in accordance with the<br />

definitions given in American Society for Testing and Materials (ASTM) designations<br />

D3753-99. The resin used shall be of a commercial grade and shall be evaluated as a<br />

laminate by test or determined by previous service to be acceptable for the environment.<br />

The resins used may contain the minimum amount of fillers or additives required to<br />

improve handling properties. Up to 5% by weight of thixotropic agent that will not<br />

interfere with visual inspection may be added to the resin for viscosity control. The<br />

laminate shall consist of an inner surface, an interior layer, and an exterior layer of laminate<br />

body. A White GelCoat shall be the finishing surface for the interior of the Wet Well /<br />

Valve Vault. The Wet Well / Valve Vault must be designed to withstand wall collapse<br />

based on the assumption of hydrostatic type loading by backfill with a density of 120<br />

lb./ft. 3 . The tank wall laminate must be constructed to withstand or exceed. The Wet Well<br />

shall incorporate an integral Hopper Bottom design that directs solids into the center of the<br />

wet well and into the suction of the pumps.<br />

2. Reinforcement: The Wet Well bottom of 8ft diameter or larger Wet Wells shall be<br />

constructed of .50 inch A36 steel plate minimum. 6-in I-beams shall be welded to the .50<br />

inch steel plate to add structural integrity and reduce the possible deflection caused from up<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221329-6