Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

Hardware Points Software Points<br />

Point Name AI AO BI BO AV BV Sched Trend Alarm<br />

Show On<br />

Graphic<br />

Supply Air Temp × × ×<br />

Cooling/heating Valve × × ×<br />

Fan VFD Speed × × ×<br />

Fan VFD Fault × × ×<br />

Fire Alarm Control Panel signal x x<br />

Building Sludge Loading Bay<br />

Supply Air Flow Setpoint<br />

Building Sludge Loading Bay<br />

Supply Air Flow<br />

High Building Sludge Loading Bay<br />

Supply Air Flow<br />

Low Building Sludge Loading Bay<br />

Supply Air Flow<br />

× × ×<br />

× × ×<br />

Supply Air Smoke Detector × × × ×<br />

Supply Fan Status × × ×<br />

Supply Fan Start/Stop × × ×<br />

Mixed Air Dampers × ×<br />

Environmental Index × × ×<br />

Percent of Time Satisfied × × ×<br />

Heating Setpoint × ×<br />

Cooling Setpoint × ×<br />

High Zone Temp × ×<br />

Low Zone Temp × ×<br />

Supply Fan Failure ×<br />

Supply Fan in Hand ×<br />

Supply Fan Runtime Exceeded ×<br />

Prefilter Change Required × ×<br />

Final Filter Change Required × ×<br />

High Return Air Temp × ×<br />

Low Return Air Temp × ×<br />

High Supply Air Temp × ×<br />

Low Supply Air Temp × ×<br />

Totals 7 2 4 2 3 0 0 16 16 27<br />

Total Hardware ( 15 ) Total Software ( 34 )<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230993 - 6<br />