Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

13. Weld Maps: Formal sketches, design drawings, or shop drawings that show the location<br />

of welds in a system, so that documentation (i.e., Certified Material Test Reports, Welder<br />

Identification, and Weld Examination Records) can be traced to the weld it represents.<br />

14. Welder Performance Qualification (WPQ): The record which documents a Welder's successful<br />

completion of a performance qualification test and establishes the range of variables<br />

the Welder is qualified for.<br />

15. Welding Procedure Specification (WPS): a document providing in detail the required variables<br />

for a specific welding application to assure repeatability by properly trained welders<br />

and welding operators<br />

16. Work Package (WP): Consists of a collection of forms, documents, procedures, work instructions,<br />

etc. necessary to support a certain scope of work.<br />

17. WQ&I: Welder Qualification and Inspection<br />

1.6 PERFORMANCE REQUIREMENTS<br />

A. General Design Requirements and Conditions for the Low Pressure Air Purge and Process Condensate<br />

Drain Piping System:<br />

1. Normal operating pressure at 7 psig, maximum.<br />

2. Normal design pressure of 10 psig.<br />

3. Normal operating temperature at 68 deg F.<br />

4. Normal design temperature at 100 deg F.<br />

5. Normal operating flow rate at 150 scfm, maximum.<br />

6. Fluid properties are the same as Air at 68 deg F.<br />

7. Piping Code Low pressure system: ASME B31.3, Normal Service.<br />

B. Manufacturer Seismic Qualification Certification: Submit certification that Low Pressure Air<br />

Purge Piping, accessories, and components will withstand seismic forces defined in Section<br />

220548, Vibration and Seismic Controls for Plumbing Piping and Equipment. Include the<br />

following:<br />

1. The term "withstand" means "the unit will remain in place without separation of any parts<br />

from the device when subjected to the seismic forces specified."<br />

2. Basis for Certification: Indicate whether withstand certification is based on actual test of<br />

assembled components or on calculation.<br />

3. All pipe installation isometrics and vendor specific data necessary for pipe stress analysis<br />

(including flange leakage analysis data) shall be supplied by the Seller to the Buyer for<br />

review 30 days prior to scheduled installation date.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 431510 - 8